Technical data
27
©1995 Square D—All Rights Reserved
11/98
Accessories
06313053
06313054
12 14
OF
22 24 32 34 42 44
Closed
Open
11 21 31 41
Time-delayed Undervoltage Trip Device (MNR) (1)
To prevent the circuit breaker from tripping in the event of transient voltage drops, this release has a
built-in adjustable time delay. If required, this time delay can be overridden by connecting an
external switch on an additional circuit (wired by the user). The undervoltage trip device is field-
installable.
MN MNR (1)
Control Voltage (V)
60 Hz 120 120
240 —
480 480
DC 24 —
48 —
125 —
250 —
Consumption (Inrush and Sealed)
AC 20 VA 20 VA
DC 15 W 15 W
Operating Time (s)
0.09 0.5–0.9–1.5–3
(1) Not UL Listed.
Heavy Usage Auxiliary Switches (OF)
Four SPDT switches with double break construction. They are directly operated by the main
contacts and ensure a large insulation distance in open position. They are therefore particularly
suitable for insulation of auxiliary circuits or reliable interlockings.
n "a" contacts are open when the circuit breaker is open and closed when the circuit breaker is
closed.
n "b" switches are closed when the circuit breaker is open and open when the circuit breaker is
closed.
See page 30 for operating diagrams. Auxiliary switches are field-installable.