Technical data

11/98
©1995 Square DAll Rights Reserved
26
Accessories
06313049
0631305106313052
C2
C1
MX
Remote
Open
D4
D1
Remote
Open
MN
Instantaneous Undervoltage Trip Device (MN)
This release instantaneously opens the circuit breaker when supply voltage drops below a value
between 35% and 70% of rated voltage. If the release is not energized, the circuit breaker cannot
be closed (either manually or electrically). Any attempt to close it will have no effect on the main
contacts. Closing is possible when the release voltage reaches 85% of its rated value. The
instantaneous undervoltage trip device is field-installable.
Control Voltage (V)
60 Hz 120–240–480
DC 24–48–125–250
Consumption (Inrush and Sealed)
AC 20 VA
DC 15 W
Operating Time 40 ms
Opening Coils
Three types of voltage releases can be used for remote opening of the circuit breakers:
n Shunt trip (MX)
n Instantaneous undervoltage trip device (MN)
n Time-delayed undervoltage trip device (MNR)
Possible Combinations
Each MASTERPACT circuit breaker can be equipped with:
n One shunt trip (MX) + one undervoltage trip device (MN or MNR)
n Or two shunt trips (MX)
Shunt Trip (MX)
This release is rated for continuous duty and operates with control voltages between 85% and 110%
of its rating. However, when series connected with an "a" auxiliary switch, the shunt trip can be
operated with 55% or more of its rated voltage and can be used for ground-fault protection when
combined with a Class 1 ground-fault sensing element. The shunt trip is field-installable.