Technical data
11/98
©1995 Square D—All Rights Reserved
20
Control Units
DC150 Data Concentrator
Function
The DC150 data concentrator is used to:
n Centralize all the information supplied by the various communicating devices:
o Auxiliary switches and motor operator
o SC150 indication and control interface
n Make information available to a personal computer or programmable logic controller (PLC) via the
MODBUS/JBUS protocol
n Log status changes and tripping of the communicating circuit breakers in order to provide the
user with a list of time-stamped events
n Supply the 24 V and 15 V power required by the communicating devices and the internal bus
n Carry out addressing for the communicating devices
Each DC150 data concentrator can be connected to a maximum of 48 instrumented outgoing or
incoming circuits.
06313039
Information or Function Managed by the DC150 Data Concentrator
Information Transmitted or Devices Required to Display the Information or
Function Carried Out Carry Out the Function
Display Device Status: Circuit Breaker or Other Power-circuit Actuator
n On, Off, Tripped, Tripped Due to Electrical Fault, o COMPACT NS Circuit Breaker + Communicating Auxiliary Switches
Connected, Disconnected o COMPACT/MASTERPACT Circuit Breaker + SC150 Indication and Control
Interface
o COMPACT NS Circuit Breaker + Communicating Auxiliary Switches
o MULTI 9 Control Device + ATB Interface
n Tripped Due to Ground Fault o COMPACT NS Circuit Breaker + Vigi or Ground-fault Relay + SC150
Indication and Control Interface
Remotely Operate a Circuit Breaker n COMPACT NS Circuit Breaker + Communicating Motor Operator
(On, Off or Reset) n COMPACT/MASTERPACT Circuit Breaker + SC150 Indication and Control
Interface
n MULTI 9 Control Device + ATB Interface
Inhibit Reset Following Tripping Due As Above
to Electrical Fault
Select Operating Mode of Motor As Above + CLS150 Indication and Local Control Module
Operators (Local or Remote)
Measure Currents (Phases and Neutral) COMPACT/MASTERPACT Circuit Breaker Equipped with Electronic Control Unit
Comprising Communications Option + SC150 Indication and Control Interface
Count Number of Operating Cycles SC150 Indication and Control Interface
Display Causes of Tripping COMPACT/MASTERPACT Circuit Breaker Equipped with Electronic Control Unit
Comprising Communications Option + SC150 Indication and Control Interface
Display Trip Alarm for Long-time Fault As Above
Display Trip Unit Settings As Above
(Thresholds and Time Delay)
Junction Block
06313041
Internal Bus Cable
06313042
RS232/RS485 Converter
06313040
Accessories
Connection Cable for Internal Bus Cat. No. 50779 65 ft. (20 m)
or 50780 330 ft. (100 m)
Junction Block for Internal Bus Cat. No. 50778
RS485/RS232 Conversion Unit Cat. No. 50786
Connection to Personal Computer An RS232/RS485 converter is required for connection to a personal computer
equipped with an RS232 output to the MODBUS/RS485 bus.
Connector
06313116