Technical data

11/98
©1995 Square DAll Rights Reserved
16
Control Units
Test Kits
Every control unit is equipped with a test receptacle that can be used with a test kit. Tests
performed by test kits are only functional tests designed to electrically test the operating integrity of
the control unit, the flux transfer device and the mechanical operation of the circuit breaker. Tests
are not designed to calibrate the circuit breaker. Calibration can only be done at the factory.
06313035 06313034
Load monitoring (R)
Option R provides two independent static contacts which operate when the current exceeds
adjustable pickup limits:
n When the current exceeds the limit Ic1 (or Ic2), the contact C-R1 (or C-R2) closes following an
inverse time characteristic A.
n When the current drops below the limit Ic1 (or Ic2), the contact C-R1 (or C-R2) opens with
constant time delay (10 seconds) B.
These contacts can be used for load shedding, alarms, indications, etc.
Voltage 240 Vac max.
Outputs 0.1 A triac
06313036
xIn
i
R
push to reset
I1 I2 I3
90%
50%
20%
STR 58 U
Ir tr
xIo at 1.5Ir
Im tm
xIo
t
test
F
test
I
xIr xIr
T
Ih th
xIn
Ic1 Ic2
06313033
Mini Test Kit
Calibration Test Kit
I
t
Long-time
B
A