Specifications

E5CN
E5CN
CHARACTERISTICS
Indication accuracy Thermocouple:
( 0.5% of indicated value or 1 C, whichever greater) 1 digit max. (See Note.)
Platinum resistance thermometer:
( 0.5% of indicated value or 1 C, whichever greater) 1 digit max.
Analog input: 0.5% FS 1 digit max.
CT input: 5% FS 1 digit max.
Hysteresis 0.1 to 999.9 EU (in units of 0.1 EU)
Proportional band (P) 0.1 to 999.9 EU (in units of 0.1 EU)
Integral time (I) 0 to 3999 s (in units of 1 s)
Derivative time (D) 0 to 3999 s (in units of 1 s)
Control period 1to99s(inunitsof1s)
Manual reset value 0.0% to 100.0% (in units of 0.1%)
Alarm setting range -1999 to 9999 (decimal point position depends on input type)
Sampling period 500 ms
Insulation resistance 20 M min. (at 500 VDC)
Dielectric strength 2000 VAC, 50 or 60 Hz for 1min (between different charging terminals)
Vibration resistance 10 to 55 Hz, 10 m/s
2
for 2 hours each in X, Y and Z directions
Shock resistance 300 m/s
2
, 3 times each in 3 axes, 6 directions (relay: 100 m/s
2
)
Weight Approx. 150 g Mounting bracket: Approx. 10g
Protective structure
Front panel NEMA4 for indoor use (equivalent to IP66)
Rear case IP20
Terminals IP00
Memory protection EEPROM (non-volatile memory) (number of writes: 100,000)
EMC Emission Enclosure: EN55011 Group 1 class A
Emission AC Mains: EN55011 Group 1 class A
Immunity ESD: EN61000-4-2: 4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference: ENV50140: 10 V/m (amplitude modulated,
80MHzto1GHz)(level3)
10 V/m (pulse modulated, 900 MHz)
Immunity Conducted Disturbance: ENV50141: 10 V (0.15 to 80 MHz) (level 3)
Immunity Burst: EN61000-4-4: 2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Approval standards UL3121-1, CSA22.2 No. 14, E.B.1402C
Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC1010-1)
Conforms to VDE0106/part 100 (Finger Protection), when the terminal cover is mounted.
Note: The indication of K thermocouples in the -200 to 1300°C range, and T and N thermocouples at a temperature of -100°C or less,
and U and L thermocouples at any temperature is ±2°C±1 digit maximum. The indication of B thermocouples at a temperature of
400°C or less is unrestricted.
The indication of R and S thermocouples at a temperature of 200°Corlessis±3°C±1 digit maximum.