Specifications
E5CN
E5CN
Specifications
RATINGS
Supply voltage 100 to 240 VAC, 50/60 Hz 24 VAC, 50/60 Hz/24 VDC
Operating voltage range 85% to 110% of rated supply voltage
Power consumption E5CN 7VA 4VA/3W
Sensor input Thermocouple: K, J, T, E, L, U, N, R, S, B
Platinum resistance thermometer: Pt100, JPt100
Non-contact temperature sensor: K10 to 70 C, K60 to 120 C, K115 to 165 C, K160 to 260 C
Voltage input: 0 to 50 mV
Control output
Relay output SPST-NO, 250 VAC, 3A (resistive load), electrical life: 100,000 operations
Voltage output 12 VDC (PNP), max. load current: 21 mA, with short-circuit protection
Alarm output SPST-NO, 250 VAC, 1 A (resistive load), electrical life: 100,000 operations
Control method PID or ON/OFF control
Setting method Digital setting using front panel keys
Indication method 7-segment digital display and single-lighting indicator
Other functions According to Controller model
Ambient temperature
-10 Cto55 C(14 F to 131 F) with no condensation or icing
Ambient humidity 25% to 85% relative humidity
Storage temperature
-25 Cto65 C (-13 F to 149 F) with no condensation or icing