Digital Temperature Controller E5CN Compact and Intelligent Temperature Controller Auto-tuning and self-tuning available.
E5CN E5CN E5CN OPTION BOARDS The E5CN provides communications or event input functionality when mounted with one of the following Option Boards. Item Function Part number Communications Board RS-485 communication E53-CNH03 Event Input Board Event input E53-CNHB Note: The heater burnout alarm is available by mounting the E53-CNH03 or E53-CNHB Option Unit on the E5CN.
E5CN E5CN INPUT RANGES Platinum Resistance Thermometer Input Shaded ranges indicate default settings. Platinum resistance thermometer input Input type Platinum resistance thermometer Temperature range Name 1800 1700 1600 1500 1400 1300 1200 1100 1000 900 800 700 600 500 400 300 200 100 0 --100 --200 Set value Pt100 JPt100 850 500.0 --200 --199.9 0 1 500.0 100.0 100.0 0.0 0.0 --199.9 2 3 4 Thermocouple Input Shaded ranges indicate default settings.
E5CN E5CN Specifications RATINGS Supply voltage 100 to 240 VAC, 50/60 Hz Operating voltage range 85% to 110% of rated supply voltage Power consumption 7 VA E5CN Sensor input Control output 24 VAC, 50/60 Hz/24 VDC 4 VA/3 W Thermocouple: K, J, T, E, L, U, N, R, S, B Platinum resistance thermometer: Pt100, JPt100 Non-contact temperature sensor: K10 to 70 C, K60 to 120 C, K115 to 165 C, K160 to 260 C Voltage input: 0 to 50 mV Relay output SPST-NO, 250 VAC, 3A (resistive load), electrical life: 1
E5CN E5CN CHARACTERISTICS Indication accuracy Thermocouple: ( 0.5% of indicated value or 1 C, whichever greater) Platinum resistance thermometer: ( 0.5% of indicated value or 1 C, whichever greater) Analog input: 0.5% FS 1 digit max. CT input: 5% FS 1 digit max. 1 digit max. (See Note.) 1 digit max. Hysteresis 0.1 to 999.9 EU (in units of 0.1 EU) Proportional band (P) 0.1 to 999.9 EU (in units of 0.
E5CN E5CN COMMUNICATIONS SPECIFICATIONS Transmission path connection Multiple points Communications method RS-485 (two-wire, half duplex) Synchronization method Start-stop synchronization Baud rate 1,200/2,400/4,800/9,600/19,200 bps Transmission code ASCII Data bit length 7 or 8 bits Stop bit length 1 or 2 bits Error detection Vertical parity (none, even, odd) Frame check sequence (FCS): with SYSMAC WAY Block check character (BCC): with CompoWay/F Flow control Not available Interface
E5CN E5CN Nomenclature E5CN Operation Indicators 1. AL1 (alarm 1) Lights when alarm 1 output is ON. AL2 (alarm 2) Lights when alarm 2 output is ON. 2. HB (heater burnout alarm display) Lights when a heater burnout is detected. The heater burnout alarm remains ON by setting the heater burnout latch. To reset, turn the power supply OFF and then ON or set the heater burnout alarm value to “0.0A.” 3.
E5CN E5CN Operation INITIAL SETUP On previous Controllers, sensor input type, alarm type and control period were set on DIP switches. These hardware settings are now set in parameters in setup menus. The and keys are used to switch between setup menus, and the amount of time that you hold the keys down determines which setup menu you move to. This section describes two typical examples. Note: On the E5GN, the Key is the 1. ON/OFF Control Typical Application Examples Key.
E5CN E5CN 2. PID Control Using Auto-tuning Typical Application Example • Typical Example Changing Parameters Input type: 4 T thermocouple -200 to 400°C Control method: PID control ST (self-tuning): OFF Calculate PID constants by AT (auto-tuning). Alarm type: 2 upper limit Alarm value 1: 30°C (For setting deviation) Set point: 150°C indicates that there is a parameter. Keep on pressing the mode key until the desired parameter is selected.
E5CN E5CN Specification Setting After Turning ON Power OUTLINE OF OPERATION PROCEDURES Key Operation In the following descriptions, all the parameters are introduced in the display sequence. Some parameters may not be displayed depending on the protect settings and operation conditions. Power ON Operation level Adjustment level + key 1 second min. key Less than 1 second key 3 second min. key 1 second min.
E5CN E5CN Communications Setting Level Calibration Level To select this level, press the key once for less than one second in the initial setting level. When the communications function is used, set the communications conditions in this level. Communicating with a personal computer (host computer) allows set points to be read and written, and manipulated variables to be monitored. To select this level, you must enter the password (“1201”) in the advanced function setting level.
E5CN E5CN SPECIFICATION SETTING (AFTER TURNING ON POWER) Initial Setting Level This level is used for setting basic specifications of the Temperature Controller. Using this level, set the input type for selecting the input to be connected such as the thermocouple or platinum resistance thermometer and set the range of set point and the alarm mode.
E5CN E5CN INPUT TYPE Using a Thermocouple Input Type When using a thermocouple input type, follow the specifications listed in the following table. Input type Specifications Set Value Input Temperature Range Thermocouple K 0 --200 to 1300 (°C) 1 --20.0 to 500.0 (°C) /0.0 to 900.0 (°F) 2 --100 to 850 (°C) 3 --20.0 to 400.0 (°C) /0.0 to 750.
E5CN E5CN ALARM 1 AND ALARM 2 For the alarm 1 and alarm 2, select alarm types out of the 12 alarm types listed in the following table.
E5CN E5CN PARAMETERS Parameters related to setting items for each level are marked in boxes in the flowcharts and brief descriptions are given as required. At the end of each setting item, press the mode key to return to the beginning of each level. Operation Level Power ON Display E5CN No. 1 display E5GN PV No. 1 display Add in the “additional PV display” parameter. PV/SP No. 2 display No. 2 display Multi-SP Power ON Set point during SP ramp Operation level key 1 second min. Select SP.
E5CN E5CN Initial Setting Level Adjustment Level Input type AT execute/cancel Auto-tuning Communications writing Scaling upper limit For analog input (Input type: 16) 0- to 50-mV setting Scaling lower limit Heater current value monitor Decimal point Number of displayed digits Heater burnout detection Temperature unit Set point 0 : °C : °F : Enabled : Disabled HBA function Set point 1 Set point upper limit Limit the set point.
E5CN E5CN Advanced Function Setting Level Protect Level Operation/adjustment protection Parameter initialize Resets to the default value. Restricts display and modification of menus in the operation and adjustment levels. Initial setting/communications protection Restricts display and modification of menus in the initial setting, operation level and adjustment levels. Number of multi-SP uses Setting change protection Protects changes to setups by operating the front panel keys.
E5CN E5CN Communications Setting Level Set the E5CN/E5GN communications specifications in the communications setting level. For setting communications parameters, use the E5CN/E5GN panel. The communications parameters and their settings are listed in the following table. Parameter Displayed characters Set (monitor) value Set value Communications unit No. 0 to 99 0.1 to 99 Baud rate 1.2/2.4/4.8/9.6/19.2 (kbps) 1.2/2.4/4.8/9.6/19.
E5CN E5CN TROUBLESHOOTING When an error occurs, an error code will be displayed on the No. 1 display. Check the contents of an error and take appropriate countermeasures. Type of error Countermeasures Input error Check the wiring of inputs for miswiring, disconnections, short-circuits, and the input type. Memory error First, turn the power OFF then back ON again. If the display remains the same, the Unit must be repaired.
E5CN E5CN Dimensions Unit: mm (inch) E5CN Panel Cutouts Mounted Separately 102 (4.02) 48 x 48 9 60 min. Group Mounted +1.0 0 (48 number of units -2.5) 93 78 45 +0.6 0 44.8 58 48.8 (1.92) 60 min. 45 +0.6 0 Group mounting does not allow waterproofing. 45 Note: The suffix “500” is added to the model number of each Controller provided with a E53-COV10 Terminal Cover. • • • TERMINAL COVER E53-COV10 48 (1.89) 48.8 (1.92) 22 (0.87) 9.1 (0.36) +0.
E5CN E5CN CURRENT TRANSFORMER (SOLD SEPARATELY) E54-CT1 21 (0.83) 15 2.8 5.8 dia. 7.5 25 3 (0.98) 10.5 40 (1.57) Two, 3.5 dia. 10 30 (1.18) E54-CT3 2.36 dia. 30 (1.18) 12 dia. 9 40 x 40 Two, M3 (depth: 4) 15 (0.59) 30 (1.
E5CN E5CN Installation SETTING UP OPTION BOARDS If communications, event input, or heater burnout functions are required, mount the E53-CNH03 Communications Board or the E53-CNHB Event Input Board. The heater burnout function is supported on either of these two Option Boards.
E5CN E5CN WIRING TERMINALS The voltage output (control output) is not electrically insulated from the internal circuits. When using a grounding thermocouple, do not connect the control output terminals to the ground. If the control output terminals are connected to the ground, errors will occur in the measured temperature values as a result of leakage current. Voltage Output Control output Relay Output Standard insulation is applied to the power supply I/O sections.
E5CN E5CN Precautions OPERATING ENVIRONMENT • • • • Use the Temperature Controller within the rated operating temperature, storage temperature, and operating humidity specified for each model. Use the Temperature Controller according to the performance specifications such as vibration, shock, and degree of protection specified for each model. Do not use the Temperature Controller in places where it is subject to dust or corrosive gases.
E5CN E5CN Omron Europe B.V. EMA-ISD, tel:+31 23 5681390, fax:+31 23 5681397, http://www.eu.omron.com/ema Cat. No. GCTC12 1/99 Specifications subject to change without notice. Printed in U.S.A.