Specifications
DS7400Xi Ver. 3+ Reference Guide Copyright © 2004 Detection Systems, Inc. P/N: 28995K Page 72
be programmed for not longer than 60 seconds.
3. General Control Programming:
• Must be programmed for no swinger shunts (Program Address 0000 data digit 2, enter 0, 1, or 2).
• Program Address 0185 must be programmed as: Data Digit 1=0, Data Digit 2=0.
4. Commercial Fire Mode Programming:
• Local (Program Address 0186, data digit 1, enter as a 1 through 6).
• Central Station (Program Address 0186, data digit 1, enter as a 7 through *2).
• The keypad panic functions are not intended to be a substitute for Listed manual pull boxes.
12.6 Wiring and Programming Information for Installations Using the Ademco AB-12 Bell/Housing
1) Disconnect the wire jumper from terminal 4 to the inner housing of the Bell Box (prevents a ground fault condition).
2) Connect wiring between the control and Bell Box as shown above. To use the AB-12 Bell/Housing, cut the jumper wire “JP1” on the
control. The EOL used in the AB-12 Bell/Housing must be 27K ohms.
3) Program Zone 8 as a 24-hour zone by programming it to follow zone function 7. (Program address 0025 = 07).
4) Do not change the default programming of zone function 7. (Program address 0007 should be 22).
Control/Communicator
Cut this jumper
JP1
T
o controlAlarm Output +
T
o controlAlarm Output –
To control Zone 8 Input
To control Loop Positive
To control Earth Ground
EOL
27K
Ω
BELL
Bell Tampers
Outer Bell Box
Inner Bell Box Lining
Ademco AB-12 Bell/Housing
Terminal 1
Terminal 29 (+)
Terminal 30 (8-)
Terminal 5 (-)
Terminal 6 (A)
Alternate EOL (if not
using a Fire card)
Detection Systems’
P/N 28300