Specifications

DS7400Xi Ver. 3+ Reference Guide Copyright © 2004 Detection Systems, Inc. P/N: 28995K Page 70
50 Hz. AC input cannot be used in U. L. Listed Requirements.
The ground wire provided with the enclosure must be connected
between the “Earth GND” connection on the control and the en-
closure tab.
The keypad panic alarm output must follow the corresponding
zone function’s programming (e.g. fire = pulsing [or steady if not a
combination], burglary = steady). In all cases, the special emer-
gency keys must be silent.
The ground start feature shall not be programmed.
12.3 Programming the DS7400Xi
When used in U. L. Listed Requirements, the control must conform
to certain programming requirements. The following is a list of the
required program entries and required accessories for specific U. L.
Listed Requirements.
12.3.1 Household Fire Alarm using Digital Alarm
Communicator Transmitter with local bell
The control must be installed in accordance with NFPA 72.
Required Accessories:
At least one Detection Systems, Inc. Model DS250 Series smoke
detector with an MB Series base, DS280 Series, MX280 Series,
or another Listed compatible smoke detector.
At least one DS7480 Bell Supervision Module.
One Wheelock 46T-G10-12 bell or 34T-12 horn (will provide 85dB
for UL985 and NFPA 72 requirements; other Listed compatible
devices with a voltage range of 10.2 to 14.0 V may be used) is
required and must be installed inside the protected area.
The standard control enclosure can be used.
At least one DS7447/DS7447E or DS7445/DS7445i Keypad must
be used.
Four-wire detectors must be used with Listed power supervision
devices. A compatible Listed 4-wire detector is the Detection Sys-
tems, Inc. DS250 in an MB4W base. A compatible Listed EOL
relay is the Detection Systems, Inc. EOL200.
All zones must be used with the EOL resistor (P/N 25899), pro-
vided.
1. Report Programming:
Fire Zone Report must be programmed.
Low Battery Report (Program Address 0325) must be pro-
grammed.
AC Failure Report (Program Address 0327) must be programmed.
2. Timer Programming:
Bell Cutoff Times (Program Addresses 0195 and 0196) must be
programmed for not less than 4 minutes.
3. Zone Function Programming:
For household fire installations only, the output signal may be
pulsed or steady. For a combination system, see the selection
below on alarm output programming.
4. Alarm Output Programming:
Program Address 0146 must be programmed as: Data Digit 1=6,
Data Digit 2=3.
5. General Control Programming:
Program Address 0185 must be programmed as: Data Digit 1=0,
Data Digit 2=0.
12.3.2 Grade A Household Burglary Alarm using Digital
Alarm Communicator Transmitter with local bell
The control must be installed in accordance with U. L. Standard
UL1641.
Required Accessories:
At least one Wheelock 46T-G10-12 bell or 34T-12 horn (other
Listed compatible devices with a voltage range of 10.2 to 14.0 V
may be used) is required for this application.
The standard DS7400 enclosure can be used.
At least 1 DS7480 Bell Module
1. Report Programming:
Burglar Zone Reports must be programmed for those zones used.
Low Battery Report (Program Address 0325) must be pro-
grammed.
AC Failure Report (Program Address 0327) must be programmed.
2. Timer Programming:
Bell Cutoff Times (Program Addresses 0195 and 0196) must be
programmed for not less than 4 minutes.
Entry Delay Timer (Program Addresses 0191 and 0192) must be
programmed for not longer than 60 seconds.
Exit Delay Timer (Program Address 0193) must be programmed
for not longer than 45 seconds.
3. General Control Programming:
Program Address 0000, Data Digit 2 must be programmed for
NO Swinger Shunts (enter 0, 1, or 2).
Program Address 0185 must be programmed as: Data Digit 1=0,
Data Digit 2=0.
4. Alarm Output Programming:
Program Address 0146 must be programmed as: Data Digit 1=6,
Data Digit 2=3.
Program Address 0149 must be programmed as: Data Digit 1=8.
In a system that includes both fire alarm and burglar alarm
devices, the system must produce distinct sounds for fire
and burglar alarm conditions either by using different indi-
cating appliances or by using distinct cadences for the
same appliance.
12.4 General System Requirements
Applies to the following grades only:
Local Burglary Alarm
Grade A using Digital Alarm Communicator Transmitter (DACT)
Police Station Connection
Grades AA and A using DACT and ARDIS interface module.
Grade A using DACT and local Bell.
Central Station Burglary Alarm
Grades AA and A using DACT and ARDIS interface module.
Grade B using DACT and local bell.
Grade C using Digital Alarm Communicator Transmitter only.
The controls must be installed in accordance with U. L. Standards
UL681 and UL609 for all grades of service.
1. Report Programming:
Burglar Zone Reports must be programmed for those zones used.
Low Battery Report (Program Address 0325) must be pro-
grammed.
AC Failure Report (Program Address 0327) must be programmed.
Open Report (Program Address 0320) must be programmed.
Close Report (Program Address 0321) must be programmed.
24-Hour Check-In Reports (Program Addresses 0329 and 0336)
must be programmed.
2. General Control Programming:
The control must not be programmed for auto disarm.
Must be programmed for no swinger shunts and closing ringback.
(Program Address 0000 data digit 2, enter 0, 1, or 2).
Program Address 0185 must be programmed as: Data Digit 1=0,