Specifications
DS7400Xi Ver. 3+ Reference Guide Copyright © 2004 Detection Systems, Inc. P/N: 28995K Page 69
12.0 Installation Guide for U.L. Listed Systems
12.1 DS7400Xi U. L. Listings:
• Household Fire Alarm, U. L. Standard UL985
• Commercial Fire Alarm (Type Service: Local, Central Station, Remote Station; Type Initiating: Automatic, Manual, Sprinkler Superviso-
ry, and Waterflow), U. L. Standard UL864
• Household Burglary Alarm, U. L. Standard UL1023
• Police Station Connection Grades AA and A, U. L. Standard UL365
• Central Station Burglary Alarm Grades AA, A, B, and C; U. L. Standard UL1610
• Proprietary Alarm Units Grades A and AA, U. L. Standard UL1076
The control panel should be installed in accordance with U. L. Standard UL681, Installation and Classification of Mercantile and Bank
Burglar Alarm Systems, or U. L. Standard UL1641, Installation and Classification of Residential Burglar Alarm Systems. It should also be
installed in accordance with NFPA 72 for Household and Commercial Fire installations.
12.1.1 U.L System Configurations
The following table shows the DS7400Xi system configuration for the various types of fire and burglar alarm service for which the product
is U. L. Listed.
12.2 Installation Considerations
• Failure to install and program the control in accordance with the requirements in this section voids the listing mark of Underwriters
Laboratories, Inc.
• The maximum standby battery capacity is 35 AH @ 12 VDC.
• The total nominal standby current must not exceed 1.5 A nor 2.5 A when in alarm.
• The control must be mounted indoors and within the protected area.
• Enclosure tamper switches (if used) must be connected to a 24-hour zone.
• Grounding must be in accordance with article 250 of the NEC (NFPA 70).
• At least one U. L. Listed keypad with zone display must be connected.
• Zones must be connected to U. L. Listed, compatible devices.
Product
UL Application
CSF-D CSF-D/RF LF CSB-A PP-AA CSB-B/C PP-A LB-A PSCB-D-A PSCB-RF-A HF/B
DS7400Xi
Standard Enclosure
Attack Enclosure
AE-TR16 Enclosure
DS7416i
AB12 Bell w/Housing
R
1
1
R
n/a
R
0
0
0
2
0
n/a
0
n/a
n/a
R
1
1
n/a
n/a
n/a
0
0
0
3
0
n/a
0
n/a
R
R
n/a
R
n/a
R
4
0
0
0
3
0
4
0
R
n/a
R
n/a
R
n/a
n/a
n/a
0
0
0
3
0
n/a
0
R
n/a
R
n/a
R
n/a
n/a
n/a
0
0
0
3
0
n/a
0
R
n/a
R
n/a
R
n/a
n/a
n/a
0
0
0
3
0
n/a
0
R
n/a
R
n/a
R
n/a
R
4
0
0
0
3
0
4
0
R
n/a
R
1
1
R
R
4
0
0
0
2
0
4
0
n/a
n/a
R
n/a
R
n/a
n/a
n/a
0
0
0
3
0
n/a
0
R
n/a
R
n/a
R
n/a
R
4
0
0
0
3
0
4
0
R
n/a
R
1
1
R
n/a
R
0
0
0
2
0
n/a
0
n/a
n/a
Configuration Codes
R
= Required
0
= Optional
n/a
= Not Applicable
1
= Standard or attack enclosure may be
used.
2
= Either enclosure may be used. Device
must be mounted to the enclosure cover,
or within 20 ft. w/wiring in conduit.
3
= Either enclosure may be used.
4
= Either the DS7420i or the DS7481
must be used to monitor the phone line
input to the control unit.
DS7420i
DS7430
DS7432
DS7433
DS7447/DS7447E
DS7460
DS7481
DS7488
DS7480
Key to Application Codes
CSF-D
= Central Station Fire w/ DACT (Digital Alarm Communications Transmitter/dialer)
CSF-D/RF
= Central Station Fire w/ DACT and Radio (DS7416i)
LF
= Local Fire
CSB-A
= Central Station Burglary, grades AA and A
CSB-B/C
= Central Station Burglary, grades B and C
LB-A
= Local Burglary, grade A
PSCB-D-A
= Police Station Connected Burglary w/DACT, grade A
HF/B
= Household (residential) Fire and Burglary
PP-A
= Proprietary grade A
PP-AA
= Proprietary grade AA
PSCB-RF-A
= Police Station Connected Burglary w/Radio (DS7416i), grades AA and A