Specifications

DS7400Xi Ver. 3+ Reference Guide Copyright © 2004 Detection Systems, Inc. P/N: 28995K Page 49
11.19 Timer Programming: Program Addresses (0191-0193, 0195-0196)
11.20 AC Fail Report Delay Programming: Program Address (0197)
The AC Fail Delay Times are programmed as Hexadecimal values. For example:
00 = Send only with next report
1 *4 = 30 minute delay
3 *2 = 60 minute delay
78 = 120 minute delay
*5 0 = 240 minute delay
*5 *5 = Random delay (at least 15 minutes, but less than 120 minutes)
(*0 - *5 are Hex values. They will display as A through F at the keypads.)
See Glossary (section 6.13) for further details.
If the DS7400Xi Version 3+ is configured as a Commercial
Fire Mode System (Address 0186 - section 1-*2) the AC
Failure Report is sent on a random basis at any time
between 6 and 12 hours after the failure of the AC Primary
power when any other report is sent to the Central Station.
This delay is to comply with NFPA-72 Section 1-5.8.7.3
which requires that the battery achieve a discharge of
between 25% and 50% before the AC Failure Report is sent.
The delay time set into Address 0197 has no affect when the
DS7400Xi is in the Commercial Fire Mode.
I
MPORTAN
T
Example:
To program the Entry Delay Time 1 for 60 seconds.
Data Digit 1 = [1], Data Digit 2 = [2].
Enter the Programmer’s Mode: [9] [8] [7] [6] [#] [0]
Enter the Program Address: [0] [1] [9] [1]
Enter Data Digit 1: [1]
Enter Data Digit 2: [2]
Enter the pound key: [#]
Program the next Address, Program a different
Address, or Exit the Programmer’s Mode.
0 to 98 minutes** Default = 04 minute
s
**1 minute intervals
0 to 51 (0 to 255 sec.*) Default = 09 (45 sec.)
Data Digit
12
Address 0191
Entry Delay Time 1
Data Digit
12
Address 0192
Entry Delay Time 2
Data Digit
12
Address 0193
Exit Delay Time
Data Digit
12
Address 0195
Fire Bell Cutoff
Data Digit
12
Address 0196
Burglary Bell Cutoff
May be forced to a different value when in
Commercial Fire Mode. See section 11.17.3.
Entry and Exit Delay Timers are in
5 second intervals (the maximum
delay time is 255 seconds).
For example:
5 sec. = 01
15 sec. = 03
20 sec. = 04
30 sec. = 06
45 sec. = 09
60 sec. = 12
255 sec. = 51
0 to 51 (0 to 255 sec.*) Default = 09 (45 sec.)
*5 second intervals
*5 second intervals
0 to 51 (0 to 255 sec.*) Default = 12 (60 sec
.)
*5 second intervals
0 to 98 minutes** Default = 04 minute
s
**1 minute intervals
Entering a value of 99
will give a bell cutoff
time of 30 seconds.
Example:
To program the AC Fail Report Delay Time to be
30 minutes.
Data Digit 1 = [1], Data Digit 2 = [*] [4].
Enter the Programmer’s Mode: [9] [8] [7] [6] [#] [0
]
Enter the Program Address: [0] [1] [9] [7]
Enter Data Digit 1: [1]
Enter Data Digit 2: [*] [4]
Enter the pound key: [#]
Program the next Address, Program a different
Address, or Exit the Programmer’s Mode.
D
a
t
a
D
i
g
i
t
12
00 through FF
Address 0197
AC Fail Report Delay
Default = 00