Specifications

DS7400Xi Ver. 3+ Reference Guide Copyright © 2004 Detection Systems, Inc. P/N: 28995K Page 43
11.9 Quick Arm Control Programming: Program Address (0169)
Quick Arm Control programming defines which partitions can
be quick armed (armed without requiring a PIN to be entered).
Example:
To program so that Partitions 1 and 2 can be quick armed, while Parti-
tions 3 through 8 can not be quick armed.
Data Digit 1 = [3], Data Digit 2 = [0].
Enter the Programmer’s Mode: [9] [8] [7] [6] [#] [0]
Enter the Program Address: [0] [1] [6] [9]
Enter Data Digit 1: [3]
Enter Data Digit 2: [0]
Enter the pound key: [#]
Program the next Address, Program a different Address, or Exit the
Programmer’s Mode.
Data Dig
it
12
0
1 2 3 4 5 6 7 8 9 *0 *1 *2 *3 *4 *5
Partition 1 Quick Arm Enabled
Select Options
Enter the Data Digit as a:
Partition 4 Quick Arm Enabled
Partition 3 Quick Arm Enabled
Partition 2 Quick Arm Enabled
0
1 2 3 4 5 6 7 8 9 *0 *1 *2 *3 *4 *5
Partition 5 Quick Arm Enabled
Select Options
Enter the Data Digit as a:
Partition 8 Quick Arm Enabled
Partition 7 Quick Arm Enabled
Partition 6 Quick Arm Enabled