Specifications
DS7400Xi Ver. 3+ Reference Guide Copyright © 2004 Detection Systems, Inc. P/N: 28995K Page 38
Step 2: Assigning a Zone Function to the Zone
In this step, a Zone function is assigned to the Zone.
11.3 Zone Programming: Program Addresses (0018-0145)
In Zone Programming, each zone is defined according to its Input (single or multiple
zone input, or a DS7465) and its Zone Function or Output function (1-15). The
DS7465’s relay is the only device that will follow the output functions; its input loop
will follow a zone function. All single and multiple zone inputs will follow a zone func-
tion. See section 6.3 for further details.
Example:
To program a Zone (Zone 1) as: a Single Zone Input (PIR) and follows
Zone Function 1.
Data Digit 1 = [0], Data Digit 2 = [1].
Enter the Programmer’s Mode: [9] [8] [7] [6] [#] [0]
Enter the Program Address: [0] [0] [1] [8]
Enter Data Digit 1: [0]
Enter Data Digit 2: [1]
Enter the pound key: [#]
Program the next Address, Program a different Address, or Exit the
Programmer’s Mode.
Data Digit
12
Single Zone Input
(zones 1-8 on the control, multiplex contacts,
sensors, RF zones, or a DS7457)
Select Option
0
1
Multiple Zone Input
(any zone that is on a DS7432, DS7433, or DS7460)
* See Output Function programming, Section 11.35
For input zones (odd numbered zones) use the
Zone Function value
For output relays (even numbered zones) use the
Output Function value*
Data Digit
1
2
2
DS7465 Connections
(the input zone or the output relay on a DS7465)
For Multiplex Smoke Detector zones use a Zone
Function programmed as a Fire Zone (with or
without verification) with Trouble on Open
Data Digit
1
2
3
MX280, MX280TH Multiplex Smoke Detectors
The DS7465 occupies two zones starting with
the odd numbered zone. The odd numbered
zone of the zone pair is the input zone. The
even numbered zone of the zone pair is the
output relay.
Data Digit
1
2
4
MX280THL Multiplex Smoke Detectors
with Low Temperature Alarm
For Multiplex Smoke Detector zones (odd
numbered zones) use a Zone Function
programmed as a Fire Zone with Trouble on Open
For Multiplex Smoke Detector Low Temperature
Alarms (Even numbered zones) use a Zone
Function programmed as a Supervisory Zone and
Trouble on Open
The MX280THL occupies two zones starting
with the odd numbered zone. The odd
numbered zone of the zone pair is the smoke
detector. The even numbered zone of the
zone pair is the Low Temperature Alarm.
DD
Options
Zone
Functio
n
Value
Enter a Zone Function Value 1 - *5
Disable a Zone 0
1
2
3
4
5
6
7
8
9-128
0018
0019
0020
0021
0022
0023
0024
0025
0026-0145
01
02
03
04
05
06
07
08
00
Zone Number Address
Zone
Function
Default
Hint:
Address = Zone Number + 17
IMPORTANT
Only zones 9-128 may be
programmed as RF zones.
If programming RF zones,
you must also program
Addresses 0166 and 0168.
IMPORTANT
With the exception of RF
zones,you may disable a
zone at any time by entering
00 into the zone address.
If the zone is an RF zone,
see Section 16.3 “Removing
RF Zones” before setting
the zone address to 00.