Specifications
DS7400Xi Ver. 3+ Reference Guide Copyright © 2004 Detection Systems, Inc. P/N: 28995K Page 36
11.0 Programming
11.1 General Control Programming: Program Address (0000)
General Control programming defines the
system-wide general operating parameters.
See Glossary (section 6.1) for further details.
** = • Normal Arming = [PIN] + [On]: If programmed, Normal Arming arms the entire system while allowing entry delays for entry/
exit zones.
• Perimeter Instant Arming = [PIN] + [No Entry] + [Perimeter Only]: If programmed, Perimeter Instant Arming arms only the
perimeter of the system and does not allow entry delays for entry/exit zones.
• Perimeter Arming = [PIN] + [Perimeter Only]: If programmed, Perimeter Arming arms only the perimeter of the system
while allowing entry delays for entry/exit zones.
• Custom Arming = [PIN] + [#] [4]: If programmed, Custom Arming allows custom arming of the system and bypasses the
zone functions specified in program address 0183.
• Maximum Security Arming = [PIN] + [No Entry] + [On]: If programmed, Maximum Security Arming arms the entire system
and does not allow entry delays for entry/exit zones.
0Select Options 1 2 3 4 5 6 7
Allow Normal and Custom Arming**
Allow Perimeter Instant Arming**
Allow Perimeter Arming**
Allow Maximum Security Arming**
Closing Ring-Back
Data Digi
t
12
Siren on Comm. Fail for Silent Zone
8 9 *0 *1 *2 *3 *4 *5
Enter the Data Digit as a:
50 Hz. operation∆
60 Hz. operation
∆ = For installations in North America, select 60 Hz. operation.
*0 - *5 are Hex values. They will display as A - F at the keypads.
4
3
0 1 2
Restore zone when Sounders Silence
Restore zone when Zone Restores
Restore zone when System is Disarmed
Allow Swinger Shunts. Send Bypass Reports
Select Options 5
Enter DD as a:
678
Allow Swinger Shunts. No Bypass Reports
Example:
To program the system-wide General Operating parameters as: allow-
ing Normal and Custom Arming, Operating at 60 Hz., and to Restore
when a Zone Restores.
Data Digit 1 = [2], Data Digit 2 = [1].
Enter the Programmer’s Mode: [9] [8] [7] [6] [#] [0]
Enter the Program Address: [0] [0] [0] [0]
Enter Data Digit 1: [2]
Enter Data Digit 2: [1]
Enter the pound key: [#]
Program the next Address, Program a different Address, or Exit the
Programmer’s Mode.