Specifications
DS7400Xi Ver. 3+ Reference Guide Copyright © 2004 Detection Systems, Inc. P/N: 28995K Page 17
6.4 Output Programming
• Latch on Any Zone Alarm: This is an output programmed to
activate upon any zone alarm (including invisible zones) and will
latch until the system has been disarmed.
- If this output responds to a fire zone, it will remain latched until
the fire reset command is performed.
• ON during Entry Pre-Alert: This is an output programmed to
activate when an entry/exit zone is violated while the system is
armed.
- It will remain activated until the system is disarmed, or until the
entry delay time has expired.
• ON for 10 seconds after [PIN] + [System Reset] is entered: This
is an output programmed to activate for 10 seconds after the fire
reset command is entered at the keypad or if a Fire Zone with
Verification activates.
- This output is intended to be used to power 4-wire smoke
detectors or any other device that requires a power interruption
to reset an alarm condition.
When Programmable Output 2 is programmed this way, it
will normally supply auxiliary power and will turn OFF for
10 seconds when the fire reset command is entered.
• ON when System is Armed: This is an output programmed to
activate when the system is armed.
• Armed Full: If selected, only fully arming the system will acti-
vate the output.
• Armed Partial: If selected, only the following arming condi-
tions will activate the output: arming with bypasses, custom
arming, force arming, any form of partial arming and perimeter
arming.
• Armed Any: If selected, any arming state will activate the out-
put.
- The output will remain activated until the system is disarmed.
• Ground Start: This is an output programmed to activate for 3
seconds when the phone line is seized. It is intended for use with
ground start phone systems that require a momentary short to
ground to obtain a dial tone.
- Connect a separate 12 VDC, DPDT relay.
- Connect both relay contact commons to ground, and connect
the Normally Open of each contact to terminal positions 13
and 16 (one to terminal 13, the other to 16) of the DS7400Xi.
- This output follows all partitions regardless of how data digit 2
of the output programming address is programmed.
- Not intended for U. L. Listed systems. Not for use with phone
line monitors.
• System Status (ready to arm): This is an output programmed to
follow the Status LED of the keypad.
- It will activate when the system is ready to arm with no zones
violated.
• Zone Alarm: This is an output programmed to activate when a
zone is in an alarm condition.
- It will remain activated until the system is disarmed or the bell
cut-off time expires.
- This output is intended to activate alarm bells and sirens.
- This will not activate from Silent or Invisible Zones.
• Zone Alarm Delayed by 20 sec.: This is an output programmed
to wait 20 seconds after a zone enters an alarm condition to
activate.
- It will remain activated until the system is disarmed or the bell
cut-off time expires.
- This output is intended to activate alarm bells and sirens, but
provides a delay to allow the user to silence the system before
it activates.
• Output Functions
Output Functions can be programmed to follow system events or
to follow one or two specific zones in a “cross-matrix” fashion
(see Input/Output Cross-Matrixing).
- These Output Functions can be programmed to control Octal
Relay outputs or Multiplex Bus outputs.
- Output Functions are programmed at addresses 1472 - 1516.
• Input/Output Cross Matrixing
Input/Output Cross Matrixing allows Output Functions to follow
the status of specific input zones (zones 1 through 99 only).
- Outputs can be programmed to follow any combination of one
or two zones, open or closed, with the system armed or
disarmed.
- If programmed to latch, the output will latch until a valid PIN is
entered at the keypad.
• Keypad Sounder Output: This is an output programmed to follow
the keypad sounder.
- It activates during the entry pre-alert and during any day monitor
alarm. It does not follow momentary keypad beeps such as
keystrokes, chimes, etc.
• Access Output: This is an output programmed to activate for 10
seconds when an access control PIN is entered at the keypad.
- Not U. L. Listed for Access Control (UL294).
• Panic/Duress Output: All outputs, including the three on-board
outputs, the Octal Relays, and the Output Functions, support a
Panic/Duress function. To assign an output as a Panic/Duress
Output, program the first data digit as “*1”. Program data digit two
for the appropriate partition(s). This output will follow Duress
activations, Keypad Emergency Keys B and C, and Invisible and
Silent Zone alarms. It will reset after being acknowledged by a
user or after the burglary bell time-out expires.
• Multiplex Bus Outputs
The DS7400Xi supports up to 20 or 40 (when using a DS7436
Multiplex Module) DS7465 Input/Output Modules.
- These modules are connected to the multiplex bus and provide
one input loop and one Form “C” output relay.
- The input loop operates the same as all other multiplex inputs.
- The output loop can be programmed to follow Output Functions.
- Multiplex Bus outputs can be bypassed using the bypass
function. If an output zone is bypassed while it is ON, it will turn
OFF. The bypass will not be removed when the system is armed
and then disarmed; it must be cancelled by entering the bypass
command again or by cancelling all bypasses.
DS7465 Module outputs will not pulse, even if programmed
to do so.
• Octal Relay Modules (DS7488)
The DS7400Xi can support two Octal Relay Modules.
- Each relay can be programmed to follow system-wide events
or Output Functions as described above.
• Solid State Output Modules (DS7489)
The DS7400Xi can support two Solid State Output Modules.
- Each output can be programmed to follow system-wide events
or Output Functions as described above.
6.5 Partition Control Programming
• Partition Control Programming: Up to eight partitions may be
used. They are assigned (program address 0165) in order.
- For example: When using only one partition, it is partition one.
When using three partitions, they are partitions one, two, and
three.