Specifications
www.pulsar.pl PowerSecurity
19
The program enables storing the read data for further analysis. Press the button to save the data in
.csv or .dat format, allowing reloading and displaying data in a chart window.
The information about the type of power supply, its position in the manager list and the communication
address can be obtained by pressing the button. This information is particularly useful when importing a file
from another PSU.
5.3.2 Reading the history of events of the power supply with LCD display.
To read the history of events of the power supply with LCD display press the button. The reading starts
from the most recent entries. The reading can be stopped at any time by pressing the button.
Fig. 19. The „History” tab.
The table of the history of events of the power supply includes information about:
Time and date – date and time of the event
Event description – event code and its description. Appendixes A, B and C at the end of the manual
summarize all the failure and event codes that may occur during the power supply operation. The individual
codes are accompanied by appropriate optical indication on the panel, acoustic indication and activation of
the dedicated technical output.
AC – AC 230V power indication:
ON = AC power on
OFF = AC power off
LB – battery charging indication
ON = battery charging
OFF = no charging, battery fully charged
EXTi – external failure input
ON = failure
OFF = normal status
EPS – technical output indicating AC power loss
Open = AC power loss
closed = AC power - OK.
PSU – technical output indicating PSU failure
open = failure
closed = PSU operation - OK
APS – technical output indicating battery failure
open = battery failure
closed = battery OK
EXTo – controlled relay output
open = output on
closed = output off
ALARM – technical output of collective failure
Open = AC power loss
closed = AC power - OK.