Installation manual

User Settings Tables
S1A53838 09/2011 175
F366 111 [PID Derivative Gain]
--
0.00 – 2.55
0.00
F380 111
[PID reverse error]
-
0
[No]
0
1
[Yes]
F391 111
[Stop on LL hyst]
Hz -
0.0 – [Max frequency] (FH)
0.2
F392 111
[PID wake up (thres)]
Hz -
0.0 – [Max frequency] (FH)
0.0
F393 111
[PID wake up, feedb]
Hz -
0.0 – [Max frequency] (FH)
0.0
F400 71
[Auto-tuning drive]
-
0
[Disabled]
0
1
[Initialize constant]
2
[Complete tune]
F401 74
[Slip Compensation]
%-
0 – 150
50
F402 74
[Auto Torque Boost]
%-
0.0 – 30.0
Model
depen-
dent
F415 70
[Motor rated current]
A-
0.1 – 200.0
Model
depen-
dent
F416 70
[Mot no-load current]
%-
10.0 – 100.0
Model
depen-
dent
F417 70
[Motor rated speed]
rpm -
100 – 15000
Model
depen-
dent
F418 75
[Frequency loop gain]
--
1 – 150
40
F419 75 [Freq. loop stability]
--
1 – 100
20
F470 107 [VIA bias]
--
0 – 255
128
F471 107 [VIA gain]
--
0 – 255
148
F472 107 [VIB bias]
--
0 – 255
128
F473 107 [VIB gain]
--
0 – 255
148
F480 72 [No load cur. coef]
--
100 – 130
100
F481 133 [In noise comp. filter]
μs-
0 – 9999
0
F482 133 [In noise Inhibit filter]
μs-
0 – 9999
442
F483 133
[In noise inhibit gain]
--
0.0 – 300.0
100.0
F484 133
[Pwr supply adj. gain]
--
0.0 to 2.0
0.0
F485 72 [Stall control coef. 1]
--
10 – 250
100
F492 72 [Stall control coef. 2]
--
50 – 150
100
F494 72
[Mot. adj coefficient]
--
DO NOT ADJUST
Model
depen-
dant
F495 72
[Motor voltage coef.]
%-
90 – 120
104
F496 72
[PWM adj. coef.]
kHz -
0.1 – 14.0
14.0
F500 83
[Acceleration time 2]
s1
0.0 – 3200
20.0
F501 83
[Deceleration time 2]
s1
0.0 – 3200
20.0
F502 84 [Acc/dec 1 pattern]
-
0
[Linear]
0
1
[S-ramp 1]
2
[S-ramp 2]
F503 84
[Acc/dec 2 pattern]
-
0
[Linear]
0
1
[S-pattern 1]
2
[S-pattern 2]
F504 85
[Ramp switching]
-
1
[Ramp 1]
1
2
[Ramp 2]
F505 85
[Commut. ramp freq.]
Hz -
0.0 – [Upper limit freq] (UL)
0.0
F506 84 [Acc/Dec S-pat start]
%-
0 – 50
10
F507 84 [Acc/Dec S-pat end]
--
0 – 50
10
Code Page Name Unit Adjustment Range / Function
Factory
Setting
User
Setting