Installation manual

User Settings Tables
174 S1A53838 09/2011
F252 88 [DC braking time]
s-
0.0 – 20.0
1.0
F256 78
[Time limit low spd]
s
0
[Disable]
0.0
1
[Enable]
F264 113
[+speed LI resp time]
s-
0.0 – 10.0
0.1
F265 113
[+speed freq. step]
Hz -
0.0 – [Max frequency] (FH)
0.1
F266 113
[- speed LI resp time]
s-
0.0 – 10.0
0.1
F267 113
[- speed freq. step]
Hz -
0.0 – [Max frequency] (FH)
0.1
F268 113
[Init +/- Speed]
Hz -
0.0 – [Max frequency] (FH)
0.0
F269 113
[Init +/- Speed memo]
-
0
[Disable]
1
1
[Enable]
F270 87
[Jump frequency 1]
Hz -
0.0 – [Max frequency] (FH)
0.0
F271 87 [Jump bandwidth 1]
Hz -
0.0 – 30.0
0.0
F272 87 [Jump frequency 2]
Hz -
0.0 – [Max frequency] (FH)
0.0
F273 87 [Jump bandwidth 2]
Hz -
0.0 – 30.0
0.0
F274 87 [Jump frequency 3]
Hz -
0.0 – [Max frequency] (FH)
0.0
F275 87 [Jump bandwidth 3]
Hz -
0.0 – 30.0
0.0
F294 79 [Forced speed freq.]
Hz -
[Low limit frequency] (LL)[Upper limit freq] (UL)
50.0
F295 78
[Switch rem/Local]
-
0
[No bumpless]
1
1
[Bumpless]
F300 85
[Switch. freq. level]
kHz -
6.0 – 16.0
Model
depen-
dent
F301 126
[Catch on fly]
-
0
[Disable]
3
1
[Brief power loss]
2
[Run restored]
3
[Power loss, run]
4
[Each start]
F302 127
[Supply loss behav.]
-
0
[Disabled]
0
1
[Do not use]
2
[Freewheel]
F303 124
[Number auto reset]
-
0
[Disabled]
3
1-10
[Number of fault reset attempts]
F305 128
[Overvoltage fault]
-
0
[Enable]
2
1
[Disabled]
2
[Quick deceleration]
3
[Dyn. deceleration]
F307 73
[Mot volt limitation]
-
0
[Motor volt limit]
3
1
[Line & mot correct.]
2
[No action]
3
[U Line correction]
F311 86
[Motor direction]
-
0
[Fw & Rev.]
1
1
[Fw only]
2
[Rev. only]
F312 86
[Noise reduction]
-
0
[Disable]
0
1
[Enable]
F316 86
[Switch. freq. mode]
-
0
[Fixed]
1
1
[Auto]
2
[460 V fixed]
3
[460 V Auto]
F320 146
[Load gain]
%-
0 – 100%
0
F323 146 [Load gain offset]
%-
0 – 100%
10
F359 111 [PID ctrl wait time]
s-
0 – 2400
0
F360 110
[PID control enable]
-
0
[No PID]
0
1
[PID by VIA]
2
[PID by VIB]
F362 110
[PID Prop Gain]
--
0.01 – 100.0
0.30
F363 110 [PID Integral Gain]
--
0.01 – 100.0
0.20
Code Page Name Unit Adjustment Range / Function
Factory
Setting
User
Setting