Installation manual

User Settings Tables
S1A53838 09/2011 173
F109 90 [VIA selection]
-
0
AI
01
LI sink
2
LI source
F110 112
[Logic Funct 2 active]
- 0 – 73
See table page 162
1
F111 90
[LI F selection]
- 0 – 72
See table page 162
2
F112 90
[LI R selection]
- 0 – 72
See table page 162
6
F113 90
[LI RES selection]
- 0 – 72
See table page 162
10
F118 90
[VIA LI selection]
- 0 – 73
See table page 162
7
F130 109
[RY Relay Function 1]
-
0 – 61,
254, 255
See table page 162
4
F132 109
[FL Relay Function]
-
0 – 61,
254, 255
See table page 162
11
F137 113
[RY Relay Function 2]
-
0 – 61,
254, 255
See table page 162
255
F139 113
[RY logic select.]
-
0
Function 1and 2
0
1
Function 1 or 2
F146 109
[RY delay]
s-
0.0 – 60.0 s
0.0
F147 110
[FL Relay delay]
s-
0.0 – 60.0 s
0.0
F160 106
[VIA rel thresh. logic]
%-
0 – 100
0
F161 106
[VIA threshold hyst.]
%-
0 – 20
3
F162 106
[VIB rel thresh. logic]
%-
0 – 100
0
F163 106
[VIB threshold hyst.]
%-
0 – 20
3
F167 115
[Freq band det range]
Hz -
0.0 to [Max frequency] (FH)
2.5
F170 74
[Mot 2 rated Freq.]
Hz -
25.0 to 200.0
50.0
F171 74
[Motor 2 rated Volt]
V
230V
model
50 to 330
230
460V
model
50 to 660
400
F172 74
[Motor 2 Volt Boost]
%-
0 – 30
Model
depen-
dant
F173 74
[Motor 2 Overload]
%/A -
10 – 100% of drive rating
100
F185 74 [Mot. 2 current limit]
%/A -
10 – 110%
110
F200 108
[Auto/man speed ref]
-
0
[Enable]
0
1
[Disable]
F201 106
[VIA ref point 1]
%-
0 – 100
0
F202 106 [VIA freq. point 1]
Hz -
0.0 – 200.0
0.0
F203 106 [VIA freq. point 2]
%
0 – 100
100
F204 106
[VIA freq. point 2]
Hz
0.0 – 200.0
50.0
F207 78
[Remote spd ref 2]
-
1
[VIA]
2
2
[VIB]
3
[HMI]
4
[Communication]
5
[+/– Speed]
F210 106
[VIB ref. point 1]
%
0 – 100
0
F211 106 [VIB freq. point 1]
Hz
0.0 – 200.0
0.0
F212 106 [VIB ref. point 2]
%
0 – 100
100
F213 106
[VIB freq. point 2]
Hz
0.0 – 200.0
50.0
F240 82
[Mot start freq.]
Hz -
0.5 – 10.0
0.5
F241 144 [Freq. pedestal]
Hz -
0.0 – [Max frequency] (FH)
0.0
F242 144 [Freq. pedestal hyst.]
Hz -
0.0 – [Max frequency] (FH)
0.0
F250 88 [DC brake start freq.]
Hz -
0.0 – [Max frequency] (FH)
0.0
F251 88 [DC braking current]
%/A -
0 – 100%
50
Code Page Name Unit Adjustment Range / Function
Factory
Setting
User
Setting