Installation manual

User Settings Tables
172 S1A53838 09/2011
tYP 62 [Parameter reset]
-
0
[No action]
0–
1
[50 Hz reset]
2
[60 Hz reset]
3
[Factory set]
4
[Trip cleared]
5
[Cumul time clear]
6
[EtYP fault reset]
7
[Save parameters]
8
[Recall parameters]
9
[Elapse time reset]
Fr 77
[Local mot. direction]
-
0
[Run FW]
0
1
[Run rev.]
2
[Run FW+rev]
3
[Run rev+FW]
ACC 83
[Acceleration time 1]
s–
0.0 – 3200
Model
depen-
dent
dEC 83
[Deceleration time 1]
s–
0.0 – 3200
Model
depen-
dent
FH 82
[Max frequency]
Hz
30.0 – 200.0
80.0
UL 82 [Upper limit freq]
Hz
0.5 – [Max frequency] (FH)
50.0
LL 82 [Low limit frequency]
Hz
0.0 – [Upper limit freq] (UL)
0.0
uL 70 [Motor rated freq.]
Hz
25.0 – 200.00
50.0
uLu 70
[Motor Rated Voltage]
V
230 V
models
50 – 330
230
460 V
models
50 – 660
400
Pt 67
[Mot cont. mode sel.]
-
0
[Constant V/Hz]
1
1
[Variable Torque]
2
[Cst V/Hz+Boost]
3
[SVC]
4
[Economy]
5
[Do not use]
6
[Do not use]
ub 68
[Motor Voltage Boost]
%–
0.0 – 30.0
Model
depen-
dent
tHr 70
[Motor thermal prot.]
%/A
10 – 100% of drive’s output current rating
100%
OLM 135
[Motor overload prot]
-
0
[Std mot. protect.]
0
1
[Std & stall mot. prot]
2
[Self cool]
3
[Slf cool stall ov.load]
4
[Forced cool prot]
5
[Forc cool stall prot]
6
[Forced cool]
7
[F cool & stall ov load]
Sr1 112
[Preset speed 1]
Hz 1
[Low limit frequency] (LL) to [Upper limit freq] (UL)
15
Sr2 112
[Preset speed 2]
Hz 1
[Low limit frequency] (LL) to [Upper limit freq] (UL)
20
Sr3 112 [Preset speed 3]
Hz 1
[Low limit frequency] (LL) to [Upper limit freq] (UL)
25
Sr4 112 [Preset speed 4]
Hz 1
[Low limit frequency] (LL) to [Upper limit freq] (UL)
30
Sr5 112 [Preset speed 5]
Hz 1
[Low limit frequency] (LL) to [Upper limit freq] (UL)
35
Sr6 112 [Preset speed 6]
Hz 1
[Low limit frequency] (LL) to [Upper limit freq] (UL)
40
Sr7 112 [Preset speed 7]
Hz 1
[Low limit frequency] (LL) to [Upper limit freq] (UL)
45
F100 114 [Freq. 1 reached]
Hz -
0.0 to [Max frequency] (FH)
0.0
F101 114 [Freq. 2 reached]
Hz -
0.0 to [Max frequency] (FH)
0.0
F102 114 [Freq.2 bandw.]
Hz -
0.0 to [Max frequency] (FH)
2.5
F108 112 [Logic Funct 1 active]
- 0 – 73
See table on page 91
0
Code Page Name Unit Adjustment Range / Function
Factory
Setting
User
Setting