Installation manual

I/O Control Parameters
S1A53838 09/2011 101
28
[Auto-reset fault]
Auto-clear detected fault
Note: Relay activates when
maximum number of autoclear set
by [Number auto reset] (F303)
page 124
is reached.
OFF: None of the detected fault conditions listed below exist
ON: One (or more) of the following
detected fault conditions exists:
Fd1 – damper detected fault 1 (closed damper)
Fd2 – damper detected fault 2 (opened damper)
OC1 – overcurrent during acceleration
OC2 – overcurrent during deceleration
OC3 – overcurrent during constant speed
OC1P – Short circuit or ground detected fault during
acceleration
OC2P – Short circuit or ground detected fault during
deceleration
OC3P – Short circuit or ground detected fault during constant
speed
OH – drive overheating
OL1 – drive overload
OL2 – motor overload
OP1 – overvoltage during acceleration
OP2 – overvoltage during deceleration
OP3 – overvoltage during constant speed
29 [Inv auto-reset flt]
Inversion of Auto-reset fault function
Note: Relay deactivates when
maximum number of autoclear set
by [Number auto reset] (F303)
page 124
is reached.
OFF: One (or more) of the following detected fault conditions exists:
Fd1 – damper detected fault 1 (closed damper)
Fd2 – damper detected fault 2 (opened damper)
OC1 – overcurrent during acceleration
OC2 – overcurrent during deceleration
OC3 – overcurrent during constant speed
OC1P – Short circuit or ground detected fault during
acceleration
OC2P – Short circuit or ground detected fault during
deceleration
OC3P – Short circuit or ground detected fault during constant
speed
OH – drive overheating
OL1 – drive overload
OL2 – motor overload
OP1 – overvoltage during acceleration
OP2 – overvoltage during deceleration
OP3 – overvoltage during constant speed
ON: None of the detected fault conditions listed above exist
30 [Drive rdy 1]
drive ready condition 1
OFF: drive not ready for operation
ON: drive ready for operation (ready includes active run permissive and ac-
tive run command)
31 [Inv drive rdy 1]
Inversion of Drive rdy 1 function
OFF: drive ready for operation (ready includes active run permissive and
active run command)
ON: drive not ready for operation
32 [Drive rdy 2]
drive ready condition 2
OFF: drive not ready for operation
ON: drive ready for operation (ready does not include active run permissive
or active run command)
33 [Inv drive rdy 2]
Inversion of Drive rdy 2 function
OFF: drive ready for operation (ready does not include active run permis-
sive or active run command)
ON: drive not ready for operation
34 [VIB ref source]
VIB input reference source
OFF: analog input terminal VIB is NOT the active speed reference source
ON: VIB is the active speed reference source
35 [Inv VIB ref source]
Inversion of VIB ref source function
OFF: analog input terminal VIB is the active speed reference source
ON: VIB is NOT the active speed reference source
Function No. / Description Action