Installation manual

I/O Control Parameters
100 S1A53838 09/2011
26
[Manu reset flt.]
Non-autoresettable detected fault
OFF: None of the detected fault conditions listed below exist
ON: One (or more) of the following detected fault conditions exists and has
stopped the drive:
E – external detected fault
E-18 – VIA analog input signal detected fault
E-19 – main control board CPU communication
E-20 – excessive torque boost
E-21 – main control board CPU detected fault 2
EEP1 – main control board EEPROM detected fault 1
EEP2 – main control board EEPROM detected fault 2
EEP3 – main control board EEPROM detected fault 3
EF2 – ground detected fault
EPH0 – output phase detected fault detection
EPH1 – input phase detected fault detection
Err1 – speed reference
Err2 – main control board RAM
Err3 – main control board ROM
Err4 – main control board CPU detected fault 1
Err5 – serial communication control
Err7 – motor current sensor
Err8 – serial communication network
Err9 – graphic display option communication interruption
Etn1 – auto-tuning
EtYP – drive ratings
OCA – short-circuit detected in drive output inverter stage
during motor startup
OCL – short-circuit detected in motor or output wiring during
motor startup
OH2 - external overheating
Ot – overtorque
Uc – underload
UP1 - Undervoltage
27
[Inv manu reset flt.]
Inversion of Manu reset flt. function
OFF: One (or more) of the following fault conditions exists and has stopped
the drive:
E – external detected fault
E-18 – VIA analog input signal
E-19 – main control board CPU communication
E-20 – excessive torque boost
E-21 – main control board CPU detected fault 2
EEP1 – main control board EEPROM detected fault 1
EEP2 – main control board EEPROM detected fault 2
EEP3 – main control board EEPROM detected fault 3
EF2 – ground fault
EPH0 – output phase loss detection
EPH1 – input phase loss detection
Err1 – speed reference
Err2 – main control board RAM
Err3 – main control board ROM
Err4 – main control board CPU detected fault 1
Err5 – serial communication control
Err7 – motor current sensor
Err8 – serial communication network
Err9 – graphic display option communication interruption
Etn1 – auto-tuning
EtYP – drive ratings
OCA – short-circuit detected in drive output inverter stage
during motor startup
OCL – short-circuit detected in motor or output wiring during
motor startup
OH2 - external overheating
Ot – overtorque
Uc – underload
UP1 - Undervoltage
ON: None of the detected fault conditions listed above exist
Function No. / Description Action