Setup guide
Dedicated Micros ©2007
58
BX2
Nuisance count
This is a repetitive detector value and is part of the advanced alarm feature. When an alarm is received on the
unit it will store the alarm time and will monitor the number of times the same detector is triggered within an
hour period. If the detector is triggered the number of times that has been set for the nuisance count then the
unit will de-activate this detector from triggering an alarm on the system for an hour.
The unit will continue to monitor the detector and check how many times it is triggered during this hour, if
it is triggered the same number as the nuisance counter it will remain de-activated for another hour, this
will continue until the trigger value goes below the nuisance count setting.
Stuck time
If any of the alarms/detectors are active for a period longer than specied in the stuck time setting then these
detectors will automatically be omitted.
This is part of the Advanced Alarms function and is set in minutes.
Pulse extension
A pulse extension (000 - 999 seconds) can be added to each alarm input.
A pulse extension extends the trigger period to avoid double alarm triggers from occurring, i.e. If a second
trigger occurs on the same alarm input within the pulse extension time period, the unit will not create a new
event.