28 10 00 33
Electronic Access Control/Intrusion Detection
Control Panels shall be capable of being configured in either repeat mode (serial) or in multi-drop
mode. When in repeat mode, the distance between the control panels may not exceed 4000 feet.
The control panels shall need to be communicating at 57,600 baud, without the use of modems or
line drivers.
e. Battery Backup: As a standard, the Access Control Panels shall include at least 4 hours of battery
backup (7AH). They shall also include internal battery backup to maintain controller database,
program, time and date during a power loss.
f. Diagnostic LED’s: The Access Control Panels shall have an LED display to indicate power, and
transmission/receipt of programmed data.
7. Hardware Features and Options:
a. Card Readers: At least 16 supported
b. Keypads: Allowed for PIN Code entry by users
c. Inputs: At least 24 supervised alarm inputs can be monitored without the need for any additional
hardware
d. Outputs: Without the need for any additional hardware, at least 17 user definable form C relay
outputs can be controlled
e. Alarm Expander Board: Up to 3 expander boards allowed, each can have a minimum of 16
supervised inputs
f. Relay Expander Board: Up to 3 expander boards allowed, each can have a minimum of 16 Form C
inputs Up to 3 expander boards allowed, each can have a minimum of 16 Form C relay outputs and
8 inputs
g. Memory Expansion Additional Memory module [256k,2Mb or 4Mb] shall be available, allowing
expansion up to 1,000,000 cards
VV. PRODUCT SUBSTITUTIONS
1. Substitutions: No substitutions permitted.
PART 3 EXECUTION
3.01 INSTALLATION
A. General: The contractor shall install all system components and appurtenances in accordance with Continental
Access’ instructions, and shall furnish all necessary interconnections, services, and adjustments required for a
complete and operable system as specified and shown. Control signal, communications, and data
transmission line grounding shall be installed as necessary to preclude ground loops, noise, and surges from
adversely affecting system operation. Provide mounting hardware as required.
B. Installation: All low voltage wiring outside the control console, cabinets, boxes, and similar enclosures, shall be
plenum rated where required by code. Cable shall not be pulled into conduits or placed in raceways,
compartments, outlet boxes, junction boxes, or similar fittings with other building wiring.
C. Device Wiring and Communication Circuit Surge Protection: All inputs shall be protected against surges
induced on device wiring. Outputs shall be protected against surges induced on control and device wiring
installed outdoors, and as shown. All communications equipment shall be protected against surges induced on
any communications circuit. All cables and conductors, except fiber optics, which serve as communications
circuits from security console to field equipment, and between field equipment, shall have surge protection
circuits installed at each end.
3.02 FIELD QUALITY CONTROL
A. Site Tests and Inspections:
1. General