Product data

[Project Number] [Project Name]
[Date] [Project Location]
28 10 00 30
Electronic Access Control/Intrusion Detection
7) Door Closed
8) Door Bypass
9) Door Free Access Start/End
10) Door Open Too Long
11) Door Key Code Entry
12) Manual Door Unlock/Lock
13) Manual Door Enable/Disable
14) Low/High Watermark
15) Valid Badge
16) Valid Badge Enabled
17) Valid Badge Disabled
18) Duress Access
19) Denied Void Badge
20) Denied Facility Match
21) Denied Time Of Day
22) Denied Issue Level
23) Denied Unauthorized
24) Denied PIN Violation
25) Denied APB IN/OUT
26) Denied Escort Match
27) Denied Reissue
28) Denied Vehicle Tag Match
29) Violate Exit Override
30) Violate Entry Override
31) Violate Time Of Day Override
32) Denied Interactivity Timeout
33) Activity Link ON/OFF
7. Category Counters: The Activity Link operation shall also include 16 category counters which allow the
cardholder to trip a single or multiple activity links.
8. Watermarks: The watermark feature shall allow the system to ‘count’ the amount of cardholders/vehicles
in a particular area. The user shall have the ability to set ‘high’ and ‘low’ marks for the system to
increment and decrement the card/vehicle count. This can be used to disable a reader and disallow any
further activity into the area until the watermark drops below the preset mark.
9. Local and Global Activity linking: The system shall support both local (within the same Access Control
Panel) as well as global (spanning multiple Access Control Panels) Activity linking for maximum system
flexibility.
QQ. Alarm Event Limit:
1. This feature shall allow the user to limit the number of repeat alarm events sent from a panel within a giv-
en period of time.
a. The user shall have the ability to add a time delay on an alarm to lessen the number of alarms that
will be sent to the Pending Alerts grid for an input that remains ‘Abnormal’.
b. This time delay setting shall be configurable and shall be in minutes.
c.
RR. Variable Door Open/Shunt Time:
1. This feature shall allow the user to unlock a door, either through Manual control or a card read, for a
period as short as one second or up to one hour.
a. The system shall bypass the door input for the same time as the unlock time.
b. The system shall allow for time increments in seconds up to 59 and then in minutes only up to 60.
c. The system shall allow for the same manual control over relays.
SS. Application Programming Interface:
1. The system shall provide for an Application Programming Interface for third party integration.
2. The API shall be constructed as a standard Windows Dynamic Link Library (DLL) and will provide various
functionalities in the form of function calls.