Product data

[Project Number] [Project Name]
[Date] [Project Location]
28 10 00 21
Electronic Access Control/Intrusion Detection
c. Previous/Next: When sorting on a header there will be two buttons (PREVIOUS) and (NEXT). The
Previous button will display the previous day’s transactions. The Next button will advance you to
the next day’s events.
d. Photo/Map: If the Photo/Maps option is enabled, the system should automatically display each
user’s photo and/or map.
7. Each alert record will provide the following information:
a. Class, Description, Location, Date, Priority, and Operator that acknowledged the alert and the time
it was acknowledged either through the ACS software or the ACS stand alone map software
directly on the Map.
8. Alarm Description: Each alarm point may be defined with a plain text description of up to 40 characters.
9. Alarm Enabling: Alarm points will be enabled during user-definable time schedules and they can be
manually silenced from any workstation.
10. Additional Alarms: The system shall also generate alarms for the following:
a. Enclosure tampering
b. Access Control Panel communication loss/restore
c. Alarm tampering (supervised)
d. Alarms shall be capable of utilizing events generated by the ACS software.
11. Alarm supervision: When using supervised alarm points, the system shall monitor for “OPEN”, SHORT”,
and “GROUND FAULT” in addition to NORMAL/ABNORMAL conditions.
12. ASCII Output-CCTV Remote Control
a. Alarm points will have the capability to output an ASCII text command for CCTV switched interface.
b. This command/output will be user-definable and transmitted on alarm points going into abnormal
state, returning to a normal state, or both, and for specified reader events as well.
13. Maps/Floor Plan Assignments
a. The system operator will be able to choose to assign a floor plan to each alert/ event. This floor
plan will help in showing the exact location of the event. The system shall be capable of displaying
these floor plans automatically or manually by the operator.
b. If the event is a badge event, in addition to the floor plan, the system will be able to automatically or
manually display an image of the badge holder both from the database and live from the CCTV
interface.
c. The system operator will be able to choose to disable the floor plans function in case it is not being
used.
d. The maps shall be capable of running without the ACS software running.
e. The system operator shall be able to assign icons to devices such as:
1) doors
2) card readers
3) Cameras
4) Alarm points to include perimeter protection systems
5) Controllers
6) Automatic gates
7) Any device that is controlled by the ACS
f. The system operator shall be able to, from the map software
1) Acknowledge alarms
2) unlock doors
3) pull up live video from any camera
4) open automatic gates
14. The system operator will be able to acknowledge pending alerts one at a time or automatically
acknowledge all pending alerts.
15. The system operator will have the advantage of filtering events to display only the category of interest.
16. Event display modes:
a. Tracking Mode will allow the operator to view events activity displayed on the screen as they occur.
b. Browse Mode will prevent the incoming events from scrolling on the screen. The highlighted event
the operator wishes to dwell on will remain stationary on the Events grid. All events may be sorted
alphanumerically.
17. Manual Control will be available for every event, which appears in the Event or Pending Alerts Grid
display that relates to a door, relay or link.