- Control Type
- Alarms
- Duplex Control
- Slidewire Position Proportioning Control
- Velocity Position Proportioning Control
- Staged Outputs
- Retransmission
- Digital Inputs
- Remote Setpoint
- Multiple Setpoints
- Multiple Sets of PID Values
- POWERBACK
- Self Tune–POWERTUNE®
- Ramp-To-Setpoint
- Input Linearization
- Load Line
- Security
- Reset Inhibition
- Process Variable Reading Correction
- Serial Communications
- Cascade Control
- Ratio Control
- Appendix 1: Menu Flowcharts
- Appendix 2: Parts List
- Appendix 3: Troubleshooting
- Appendix 4: Calibration
- Appendix 5: Specifications
- Appendix 6: Glossary
- Appendix 7: Isolation Block Diagram
- Return Procedures and Warranty Information
- 500 Series Process Controllers User's Manual

78 Chapter 7 535 User's Manual
Applications
PID OUTPUT
PARAMETER SETTINGS
ACTION:1 = REVERSE
ACTION:2 = DIRECT
PID OFST.:1 = + VALUE
PID OFST.:2 = – VALUE
LOW OUT = 0
HIGH OUT = 100
REL. GAIN = 1.0
100%
100%
50%
100% 0%
Out 1
(Heat)
Out 2
(Cool)
Out 1
Out 2
0%
0%
Offset 2
Offset 1
Figure 7.5
Duplex with a Gap Between Outputs
Duplex with 2 reverse acting outputs
Two reverse acting outputs with: no offset, no restrictive output limits, and a
neutral relative gain with PID control.
Duplex with a gap between outputs
A reverse acting output 1 and a direct acting output 2 react with: a positive offset
for output 1 and a negative offset for output 2 (assume no restrictive output limits
and a neutral relative gain with PID control).
On the graph, a positive offset refers to an offset to the left of 50%; a negative
offset is to the right of 50%.
Figure 7.4
Duplex with Two Reverse Acting
Outputs
PID OUTPUT
100%
PARAMETER SETTINGS
ACTION:1 = REVERSE
ACTION:2 = REVERSE
PID OFST.:1 = 0
PID OFST.:2 = 0
LOW OUT = 0
HIGH OUT = 100
REL. GAIN = 1.0
100%
50%100% 0%
Out 1
(Heat)
Out 2
(Cool)
Out 2
0%
0%
Out 1