User`s manual
Table Of Contents
- 535 User's Manual
- Table of Contents
- Chapter 1: Introduction
- Chapter 2: Basic Interface
- Chapter 3: Installation
- Chapter 4: Hardware Set Up
- Chapter 5: Software Configuration
- Chapter 6: Tuning
- Chapter 7: Applications
- Control Type
- Alarms
- Duplex Control
- Slidewire Position Proportioning Control
- Velocity Position Proportioning Control
- Staged Outputs
- Retransmission
- Digital Inputs
- Remote Setpoint
- Multiple Setpoints
- Multiple Sets of PID Values
- POWERBACK
- Self Tune–POWERTUNE®
- Ramp-To-Setpoint
- Input Linearization
- Load Line
- Security
- Reset Inhibition
- Process Variable Reading Correction
- Serial Communications
- Cascade Control
- Ratio Control
- Appendix 1: Menu Flowcharts
- Appendix 2: Parts List
- Appendix 3: Troubleshooting
- Appendix 4: Calibration
- Appendix 5: Specifications
- Appendix 6: Glossary
- Appendix 7: Isolation Block Diagram
- Return Procedures and Warranty Information
- 500 Series Process Controllers User's Manual

535 User's Manual Chapter 6 67
Tuning
Access Set Up Return to Operation Next menu Next parameter Next value Access Tuning Return to Operation
+
FAST MENU
DISPLAY
+
MENU MENU
▲ ▼
MENU DISPLAYFAST
21. PROP. BND.:X
Defines the proportional band for PID set X.
R 0.1 to 999.0%
D 50.0%
22. RESET:X
Defines the integral time for PID set X.
R 1 to 9999 seconds (increments of 1)
D 20 seconds
23. RATE:X
Defines the derivative time for PID set X.
R 0 to 600 seconds
D 1 seconds
24. MAN. RST.:X (or LOADLINE:X)
Defines the manual reset (or load line) for PID set X.
R 0 to 100%
D 0%
25. TRIP:X
This defines the value that triggers a change to the Xth set of PID values.
R The process variable range
D Dependent on the process variable range
MAN.RST.:X
0
TRIP:X
(D)
RATE:X
1
RESET:X
(D)
PROP.BND.:X
(D)