User`s manual
Table Of Contents
- 535 User's Manual
- Table of Contents
- Chapter 1: Introduction
- Chapter 2: Basic Interface
- Chapter 3: Installation
- Chapter 4: Hardware Set Up
- Chapter 5: Software Configuration
- Chapter 6: Tuning
- Chapter 7: Applications
- Control Type
- Alarms
- Duplex Control
- Slidewire Position Proportioning Control
- Velocity Position Proportioning Control
- Staged Outputs
- Retransmission
- Digital Inputs
- Remote Setpoint
- Multiple Setpoints
- Multiple Sets of PID Values
- POWERBACK
- Self Tune–POWERTUNE®
- Ramp-To-Setpoint
- Input Linearization
- Load Line
- Security
- Reset Inhibition
- Process Variable Reading Correction
- Serial Communications
- Cascade Control
- Ratio Control
- Appendix 1: Menu Flowcharts
- Appendix 2: Parts List
- Appendix 3: Troubleshooting
- Appendix 4: Calibration
- Appendix 5: Specifications
- Appendix 6: Glossary
- Appendix 7: Isolation Block Diagram
- Return Procedures and Warranty Information
- 500 Series Process Controllers User's Manual

Controller Set Up
Access Set Up Return to Operation Next menu Next parameter Next value Access Tuning Return to Operation
+
FAST MENU
DISPLAY
+
MENU MENU
▲ ▼
MENU DISPLAYFAST
52 Chapter 5 535 User's Manual
7. CONFIGURE
Defines lockout status of the configuration parameters.
D UNLOCKED
• LOCKED
SER. COMM.
1. STATION
Defines the unit’s station address.
R 1 to 99
• OFF Disables the communications function
D 1
2. BAUD RATE
Defines the baud rate.
• 1200 BPS
• 2400 BPS
• 4800 BPS
D 9600 BPS
• 19200 BPS
3. CRC
Defines whether CRC (cyclic redundancy check) is being calculated.
D YES
•NO
4. SHED TIME
Defines the time interval between communications activity before the controller
determines that communications is lost (“sheds”).
R 1 to 512 seconds
D OFF
5. SHED MODE
Defines the state of the controller if communications is lost (“sheds”).
D LAST MODE Remain in automatic or manual control (last mode
before losing communications)
• MANUAL Trip to manual control
• AUTOMATIC Trip to automatic control
6. SHED OUT.
Defines the output if the unit sheds and trips to manual control. Choose values
based on the process.
Standard Control On/Off Control Velocity Prop Control
• –5 to 105% • ON • CW
D LAST OUT D OFF • CCW
D OUTS. OFF
CRC
YES
SHED TIME
OFF
CONFIGURE
UNLOCKED
SER. COMM.
STATION
1
BAUD RATE
9600
SHED MODE
LAST MODE
SHED OUT.
(D)