User`s manual
Table Of Contents
- 535 User's Manual
- Table of Contents
- Chapter 1: Introduction
- Chapter 2: Basic Interface
- Chapter 3: Installation
- Chapter 4: Hardware Set Up
- Chapter 5: Software Configuration
- Chapter 6: Tuning
- Chapter 7: Applications
- Control Type
- Alarms
- Duplex Control
- Slidewire Position Proportioning Control
- Velocity Position Proportioning Control
- Staged Outputs
- Retransmission
- Digital Inputs
- Remote Setpoint
- Multiple Setpoints
- Multiple Sets of PID Values
- POWERBACK
- Self Tune–POWERTUNE®
- Ramp-To-Setpoint
- Input Linearization
- Load Line
- Security
- Reset Inhibition
- Process Variable Reading Correction
- Serial Communications
- Cascade Control
- Ratio Control
- Appendix 1: Menu Flowcharts
- Appendix 2: Parts List
- Appendix 3: Troubleshooting
- Appendix 4: Calibration
- Appendix 5: Specifications
- Appendix 6: Glossary
- Appendix 7: Isolation Block Diagram
- Return Procedures and Warranty Information
- 500 Series Process Controllers User's Manual

535 User's Manual Chapter 5 39
Controller Set Up
Access Set Up Return to Operation Next menu Next parameter Next value Access Tuning Return to Operation
+
FAST MENU
DISPLAY
+
MENU MENU
▲ ▼
MENU DISPLAYFAST
5. 15TH. INPT.
Specifies the input signal corresponding to the 15th point.
R –9999 to 99999 Minimum is [XTH-1] INPUT
D The high end of the appropriate input range (e.g. 20.00 mA)
6. 15TH. PV
Specifies the engineering unit value corresponding to the 15th point.
R –9999 to 99999
D 0
CONTROL
For configuring the choices for the control algorithm.
1. ALGORITHM
Defines the type of control algorithm.
D PID
•PI
•PD
•P
• ON/OFF
• PID:ON/OFF For Duplex applications using PID for the first output and
on/off for the second output
2. D. SOURCE
Selects the variable for the derivative action.
D PV Derivative term will not react when setpoint changes
• DEVIATION Derivative term will react when setpoint changes
3. ACTION:1
Defines the action of the first control output.
• DIRECT
D REVERSE
4. PV BREAK
Defines the manual output level if the process variable input is lost. Choose
values based on the process type.
Standard Control On/Off Control Velocity Prop Control
• –5 to 105% • ON • CW
D 0 D OFF • CCW
D OUTS. OFF
5. LOW OUT.
Defines the lowest output value that can be achieved in automatic control.
R 0 – 100% Max is HIGH OUT
D 0%
CONTROL
15TH INPT.
(D)
ALGORITHM
PID
D. SOURCE
PV
ACTION:1
REVERSE
PV BREAK
(D)
15TH PV
0
LOW OUT
0