User`s manual
Table Of Contents
- 535 User's Manual
- Table of Contents
- Chapter 1: Introduction
- Chapter 2: Basic Interface
- Chapter 3: Installation
- Chapter 4: Hardware Set Up
- Chapter 5: Software Configuration
- Chapter 6: Tuning
- Chapter 7: Applications
- Control Type
- Alarms
- Duplex Control
- Slidewire Position Proportioning Control
- Velocity Position Proportioning Control
- Staged Outputs
- Retransmission
- Digital Inputs
- Remote Setpoint
- Multiple Setpoints
- Multiple Sets of PID Values
- POWERBACK
- Self Tune–POWERTUNE®
- Ramp-To-Setpoint
- Input Linearization
- Load Line
- Security
- Reset Inhibition
- Process Variable Reading Correction
- Serial Communications
- Cascade Control
- Ratio Control
- Appendix 1: Menu Flowcharts
- Appendix 2: Parts List
- Appendix 3: Troubleshooting
- Appendix 4: Calibration
- Appendix 5: Specifications
- Appendix 6: Glossary
- Appendix 7: Isolation Block Diagram
- Return Procedures and Warranty Information
- 500 Series Process Controllers User's Manual

Controller Set Up
Access Set Up Return to Operation Next menu Next parameter Next value Access Tuning Return to Operation
+
FAST MENU
DISPLAY
+
MENU MENU
▲ ▼
MENU DISPLAYFAST
36 Chapter 5 535 User's Manual
9. SP RAMP
Defines the rate of change for setpoint changes.
D OFF Deactivates this function
R 1 to 99999 units per hour
10. FILTER
Specifies the setting for the low pass PV1 input filter.
R 0 to 120 seconds
D 0 seconds
11. OFFSET
Defines the offset to PV1 in engineering units.
R –9999 to 99999
D 0
12. GAIN
Defines the gain to PV1.
R 0.100 to 10.000
D 1.000
13. RESTORE
Defines the control mode when a broken PV1 signal is restored.
D LAST MODE
• MANUAL
• AUTOMATIC
PV2 INPUT
1. PV2 SETUP
Defines function of PV2
D SAME.AS.PV1 All PV2 parameters are set to the same values
as PV1 (no further parameters will appear)
• NOT PV1 Enables user to enter different values for the
following PV2 parameters
SP RAMP
OFF
FILTER
0
OFFSET
0
GAIN
1.000
RESTORE
LAST MODE
PV2 INPUT
PV2 SETUP
SAME.AS.PV1