User`s manual
Table Of Contents
- 535 User's Manual
- Table of Contents
- Chapter 1: Introduction
- Chapter 2: Basic Interface
- Chapter 3: Installation
- Chapter 4: Hardware Set Up
- Chapter 5: Software Configuration
- Chapter 6: Tuning
- Chapter 7: Applications
- Control Type
- Alarms
- Duplex Control
- Slidewire Position Proportioning Control
- Velocity Position Proportioning Control
- Staged Outputs
- Retransmission
- Digital Inputs
- Remote Setpoint
- Multiple Setpoints
- Multiple Sets of PID Values
- POWERBACK
- Self Tune–POWERTUNE®
- Ramp-To-Setpoint
- Input Linearization
- Load Line
- Security
- Reset Inhibition
- Process Variable Reading Correction
- Serial Communications
- Cascade Control
- Ratio Control
- Appendix 1: Menu Flowcharts
- Appendix 2: Parts List
- Appendix 3: Troubleshooting
- Appendix 4: Calibration
- Appendix 5: Specifications
- Appendix 6: Glossary
- Appendix 7: Isolation Block Diagram
- Return Procedures and Warranty Information
- 500 Series Process Controllers User's Manual

Controller Set Up
Access Set Up Return to Operation Next menu Next parameter Next value Access Tuning Return to Operation
+
FAST MENU
DISPLAY
+
MENU MENU
▲ ▼
MENU DISPLAYFAST
34 Chapter 5 535 User's Manual
16. CONTACT 5
This defines the operation of the fifth digital input.
• REM. SETPT. Makes the remote setpoint active
• MANUAL Trips the controller to manual control
• 2ND. SETPT. Makes the second setpoint active
• 2ND. PID Makes the second set of PID values active
D ALARM ACK. Acknowledges alarms
• RST. INHBT. Deactivates the reset term
• D.A./R.A. Switches the control action
• STOP A/T Suspends the adaptive tune function
• LOCK. MAN. Locks controller in manual control
• UP KEY Remote
▲▲
▲▲
▲ function
• DOWN KEY Remote
▼▼
▼▼
▼ function
• DISP KEY Toggle between SP DEV or OUT%
• FAST KEY Activates FAST key
• MENU KEY Activates MENU key.
• COMM. ONLY Status readable only through communications
17. LOOP NAME
A 9-character message associated with the loop. The first character of the 3rd
display will be flashing. To enter message, press
▲▲
▲▲
▲ and
▼▼
▼▼
▼ keys to scroll
through character set. Press FAST key to enter the selection and move to next
digit. Press MENU key to advance to next parameter.
D LOOP ONE
PV1 INPUT
1. PV1 TYPE
Specifies the particular sensor range or input range for PV1.
T/C RTD VOLTAGE CURRENT (mA)
D J T/C D DIN RTD D 1-5 V D 4-20mA
• E T/C • JIS RTD • 0-5 V • 0-20mA
• K T/C • SAMA RTD • 0-10 mV
• B T/C • 0-30 mV
• N T/C • 0-60 mV
• R T/C • 0-100 mV
• S T/C • +/– 25 mV
• T T/C
•W T/C
• W5 T/C
• PLAT.II T/C
PV INPUT
LOOP NAME
LOOP ONE
CONTACT 5
ALARM ACK.
PV1 TYPE
J T/C
CAUTION!
Set parameter values in the presented
order—dependent parameters are
dynamically related and changing values
of one can alter the value of another.
For example, if SP LO LIM. is set to 0,
and then thermocouple type is changed
to B T/C, the SP LO LIM. value will
change to 104° (the low limit of a type B
thermocouple).