34 Chapter 5 535 User's Manual
16. CONTACT 5
This defines the operation of the fifth digital input.
REM. SETPT. Makes the remote setpoint active
MANUAL Trips the controller to manual control
2ND. SETPT. Makes the second setpoint active
2ND. PID Makes the second set of PID values active
D ALARM ACK. Acknowledges alarms
RST. INHBT. Deactivates the reset term
D.A./R.A. Switches the control action
STOP A/T Suspends the adaptive tune function
LOCK. MAN. Locks controller in manual control
UP KEY Remote
function
DOWN KEY Remote
function
DISP KEY Toggle between SP DEV or OUT%
FAST KEY Activates FAST key
MENU KEY Activates MENU key.
COMM. ONLY Status readable only through communications
17. LOOP NAME
A 9-character message associated with the loop. The first character of the 3rd
display will be flashing. To enter message, press
and
keys to scroll
through character set. Press FAST key to enter the selection and move to next
digit. Press MENU key to advance to next parameter.
D LOOP ONE
PV1 INPUT
1. PV1 TYPE
Specifies the particular sensor range or input range for PV1.
T/C RTD VOLTAGE CURRENT (mA)
D J T/C D DIN RTD D 1-5 V D 4-20mA
E T/C JIS RTD 0-5 V 0-20mA
K T/C SAMA RTD 0-10 mV
B T/C 0-30 mV
N T/C 0-60 mV
R T/C 0-100 mV
S T/C +/– 25 mV
T T/C
•W T/C
W5 T/C
PLAT.II T/C
PV INPUT
LOOP NAME
LOOP ONE
CONTACT 5
ALARM ACK.
PV1 TYPE
J T/C
CAUTION!
Set parameter values in the presented
order—dependent parameters are
dynamically related and changing values
of one can alter the value of another.
For example, if SP LO LIM. is set to 0,
and then thermocouple type is changed
to B T/C, the SP LO LIM. value will
change to 104° (the low limit of a type B
thermocouple).