User`s manual
Table Of Contents
- 535 User's Manual
- Table of Contents
- Chapter 1: Introduction
- Chapter 2: Basic Interface
- Chapter 3: Installation
- Chapter 4: Hardware Set Up
- Chapter 5: Software Configuration
- Chapter 6: Tuning
- Chapter 7: Applications
- Control Type
- Alarms
- Duplex Control
- Slidewire Position Proportioning Control
- Velocity Position Proportioning Control
- Staged Outputs
- Retransmission
- Digital Inputs
- Remote Setpoint
- Multiple Setpoints
- Multiple Sets of PID Values
- POWERBACK
- Self Tune–POWERTUNE®
- Ramp-To-Setpoint
- Input Linearization
- Load Line
- Security
- Reset Inhibition
- Process Variable Reading Correction
- Serial Communications
- Cascade Control
- Ratio Control
- Appendix 1: Menu Flowcharts
- Appendix 2: Parts List
- Appendix 3: Troubleshooting
- Appendix 4: Calibration
- Appendix 5: Specifications
- Appendix 6: Glossary
- Appendix 7: Isolation Block Diagram
- Return Procedures and Warranty Information
- 500 Series Process Controllers User's Manual

Controller Set Up
Access Set Up Return to Operation Next menu Next parameter Next value Access Tuning Return to Operation
+
FAST MENU
DISPLAY
+
MENU MENU
▲ ▼
MENU DISPLAYFAST
30 Chapter 5 535 User's Manual
SOFTWARE MENUS AND PARAMETERS
CONFIG.
1. CTRL. TYPE
Defines the type of control output(s).
D STANDARD Standard control output, no special algorithms
• POS. PROP. Position proportioning control output
• STAGED Staged outputs
• DUPLEX Duplex outputs
2. LINE FREQ
Defines the power source frequency.
• 50 HZ
D 60 HZ
3. PV SOURCE
Defines how the PV input is derived from PV1 and PV2.
D PV1 Use PV1
• 1/2:SWITCH Use PV1 until contact/com selects PV2
• 1/2:BACKUP Use PV2 if PV1 is broken
• PV1–PV2 Use PV1–PV2
• PV1+PV2 Use PV1+PV2
• AVG. PV Use the average of PV1 and PV2
• HI SELECT Use PV1 or PV2 (whichever is greater)
• LO SELECT Use PV1 or PV2 (whichever is less)
4. REM. SETPT.
Selects function of the remote setpoint.
D DISABLED
• ENABLED
5. OUTPUT 2
Defines the function of the second output.
• ALM.RLY:ON
• ALM.RLY:OFF
• RETRANS. Retransmission
• COMM. ONLY Output addressable through communication
D OFF Completely deactivates the output
CONFIG.
CTRL. TYPE
STANDARD
LINE FREQ
60 Hz
OUTPUT 2
OFF
PV SOURCE
PV1
REM. SETPT.
DISABLED
NOTE:
PV1 and PV2 can be of different types and
different range.