30 Chapter 5 535 User's Manual
SOFTWARE MENUS AND PARAMETERS
CONFIG.
1. CTRL. TYPE
Defines the type of control output(s).
D STANDARD Standard control output, no special algorithms
POS. PROP. Position proportioning control output
STAGED Staged outputs
DUPLEX Duplex outputs
2. LINE FREQ
Defines the power source frequency.
50 HZ
D 60 HZ
3. PV SOURCE
Defines how the PV input is derived from PV1 and PV2.
D PV1 Use PV1
1/2:SWITCH Use PV1 until contact/com selects PV2
1/2:BACKUP Use PV2 if PV1 is broken
PV1–PV2 Use PV1–PV2
PV1+PV2 Use PV1+PV2
AVG. PV Use the average of PV1 and PV2
HI SELECT Use PV1 or PV2 (whichever is greater)
LO SELECT Use PV1 or PV2 (whichever is less)
4. REM. SETPT.
Selects function of the remote setpoint.
D DISABLED
ENABLED
5. OUTPUT 2
Defines the function of the second output.
ALM.RLY:ON
ALM.RLY:OFF
RETRANS. Retransmission
COMM. ONLY Output addressable through communication
D OFF Completely deactivates the output
CONFIG.
CTRL. TYPE
STANDARD
LINE FREQ
60 Hz
OUTPUT 2
OFF
PV SOURCE
PV1
REM. SETPT.
DISABLED
NOTE:
PV1 and PV2 can be of different types and
different range.