User`s manual

Table Of Contents
535 User's Manual Chapter 7 103
Applications
V. RATIO CONTROL
Ratio Control is employed in mixing applications that require the materials to
be mixed to a desired ratio.
For example: A given process requires Material A to be blended with Material
B in a 2:1 ratio. Material B is uncontrolled or wild. Flow sensors/transmitters
are used to measure the flow rate of each stream. The flow signal for Material
A is wired to the process variable input, and the flow signal for Material B is
wired to the remote setpoint input of the 535.
For this example, as shown in Figure 7.21, we would set RSP RATIO to 2.0. If
the flow of Material B is measured at 50 gallons/minute, the effective remote
setpoint value would be 2 times 50, or 100. The 535 controller would try to
maintain the flow of Material A at 100. As the flow of Material B changes, the
setpoint would change accordingly, always in a 2:1 ratio.
Hardware Configuration
Set the process variable jumper and remote setpoint jumper to mA. Make
sure that both inputs are set up to accept the corresponding signal from the
flow transmitters.
Wire as in Figure 7.21.
Software Configuration
1. Make sure that the range of both inputs matches the range of the
corresponding transmitter:
1
2
3
4
5
6
7
816
15
14
13
12
11
10
9
17
18
19
20
21
22
23
24
32
31
30
29
28
27
26
25
BOTTOM
(As viewed from rear)
EARTH GND
PV 1+
PV 1
AC+
AC
OUT 1
OUT 1+
MIXER
CONTROLLED STREAM
RSP+
RSP
flow
sensor
WILD STREAM
MATERIAL B
MATERIAL A
flow
sensor
Figure 7.21
Ratio Control in Mixing Applicatoin