Specifications

Multi-Zone Gas Monitors
62 P/N: 3015-5074 Rev 13
Register
Address
Description Type Range
3094 ALARM ACK ZONE 15 UNSIGNED INT 1=ACK 0=NACK
3095 ALARM ACK ZONE 16 UNSIGNED INT 1=ACK 0=NACK
3096 ALL ALARM ACK UNSIGNED INT 1=ACK 0=NACK
B.5. Block Mode Register Summary
B.5.1. Summary of Registers
Register
Name Number
HEX Decimal Description
System Data 0x0010 16 R/W System Setup Data
Status 0x0011 17 R/W Operating summary of faults, alarms and status
Zone Data 0x12xx 4609-4630 R/W Setup data for up to 16 zones (xx defines zone number)
CAL Data 0x0014 20 R/W Cal Factors for all gases
Date/Time 0x0015 21 R/W Set MZ date & time
Sensor Data 0x0016 22 R Raw measurement of sensors
Rel. Hold 0x0017 23 W Release MZ out of hold mode
Hold Zone 0x0018 24 W Put MZ into hold mode
Fault Log 0x19xx 6400-6401 R 20 most recent fault events (xx = 00 or 01)
Flow Log 0x001F 31 R 20 most recent flow fault events
Alarm Log 0x1Axx 6656-6658 R 20 most recent alarm events (xx = 00, 01, or 02)
Serv. Mode 0x001B 27 W Puts MZ into service mode
Rel Serv. 0x001C 28 W Release MZ from service mode
PPM 0x001E 30 R PPM values for all zones
Zone Log 0x3yxx 0-6
Trend data for each MZ zone [y = zone # (starting at 0), xx = 00 06]
Data
Data Type Abbreviations
C Character
Float Floating Point
I Integer
TIM Time
UI Unsigned Integer
B.5.2. System Data Register 0x0010 (16 Dec) (R/W, 54 Bytes)
Variable Type Length Description
Type UI 2 bytes Indicates EEPROM has been initialized if value = 300 DO NOT MODIFY
REV Float 4 bytes Firmware Rev Level DO NOT MODIFY
UNUSED UI 2 bytes Firmware Serial Number DO NOT MODIFY
Node UC 1 byte
Network Slave Node # (valid values are 1-15). The default is that
indicated by the Node DIP Switch on main board.
Location C 13 bytes Array defining text name of unit
Stop_Bits C 1 byte
Number of stop bits used in the MZ data stream. Default = 1. Other
available value is 2