Technical data

7. MAINTENANCE / CARE
7.1 General
Maintenance of the unit for the end user is limited to the periodic cleaning of the filters and
the intake / exhaust air valves and grilles. Twice a year, the texts “FIL” followed by “tEr”
appear alternately on the display as a reminder to clean the filters. Cleaning of the valves /
grilles is recommended at the same time as the cleaning of the filters. The system must not
be operated without filters. Switch off the unit at the three-position switch or mains power
switch before changing the filters.
7.2 Filter Changing
Fig. 9 - 1
Change the filters at least once a
year.
To change or clean the filter, loosen
the 6 screws (A). In the case of
ceiling-mounted units, the
condensate drain must also be
removed. Then remove the front
cover.
The unit is equipped as standard with
an outside air filter (A) and an
exhaust air filter (B) of Class G4.
Pull the filters out of the unit from the
front and clean using a vacuum
cleaner or replace.
Push the filter into the holder again
and check that it is seated correctly.
Fit the front cover again and secure it
with the screws. In the case of
ceiling-mounted units, fit the
condensate siphon again.
Switch on the unit again and cancel
the filter change display with the
button OK.
B
A
C