Technical data

5.2 Programming Example
Set the speed level “2” (normal ventilation) of the air intake fan to 40.
Number Button Display Description
1
Menu
P1 No function
2
P2 Time delays for forced ventilation
3
" 1 -- -- " Access code necessary (352)
4
" ? -- -- " First digit of code
5
OK
" -- ? -- "
6
" -- ? -- " Second digit of code
7
OK
" -- -- ?."
8
" -- -- ? " Third digit of code
9
OK
P3 Ventilation levels
10
OK
P31 Exhaust air fan “Low”
11
P35 Select P35
12
OK
50 Current setting
13
40 Select 40
14
OK
P35 Saves the value 40
15
MENU
P3
16
MENU
1, 2 or 3 Depending on the fan speed level
5.3 Setting Parameters
P1 No function
P2 Time delays
Number Meaning Min Max Default Unit
21
Starting delay Level 3
(floating contact)
0 15 5
Min
22
Stopping delay Level 3
(floating contact)
0 120 30
Min
P3 Fan speed levels
Number Meaning Min Max Default Unit
31
Exhaust air fan Level 1
15 98 30 %
32
Exhaust air fan Level 2
16 99 50 %
33
Exhaust air fan Level 3
17 100 90 %
34
Intake air fan Level 1
15 89 30 %
35
Intake air fan Level 2
16 99 50 %