Technical data
5.2 Programming Example
Set the speed level “2” (normal ventilation) of the air intake fan to 40.
Number Button Display Description
1
Menu
P1 No function
2
▲
P2 Time delays for forced ventilation
3
▲
" 1 -- -- " Access code necessary (352)
4
▲
" ? -- -- " First digit of code
5
OK
" -- ? -- "
6
▲
" -- ? -- " Second digit of code
7
OK
" -- -- ?."
8
▼
" -- -- ? " Third digit of code
9
OK
P3 Ventilation levels
10
OK
P31 Exhaust air fan “Low”
11
▲
P35 Select P35
12
OK
50 Current setting
13
▼
40 Select 40
14
OK
P35 Saves the value 40
15
MENU
P3
16
MENU
1, 2 or 3 Depending on the fan speed level
5.3 Setting Parameters
P1 No function
P2 Time delays
Number Meaning Min Max Default Unit
21
Starting delay Level 3
(floating contact)
0 15 5
Min
22
Stopping delay Level 3
(floating contact)
0 120 30
Min
P3 Fan speed levels
Number Meaning Min Max Default Unit
31
Exhaust air fan Level 1
15 98 30 %
32
Exhaust air fan Level 2
16 99 50 %
33
Exhaust air fan Level 3
17 100 90 %
34
Intake air fan Level 1
15 89 30 %
35
Intake air fan Level 2
16 99 50 %