System information
ATS 2000/3000/4000/4500 Programming manual 63
Warning Time Is Set To (Min) 15
Time:
Disarmed Alm Delay Time Set To (Sec). 60
Time:
Suspicion Time Is Set To (Sec). 15
Time:
Service Time Is Set To (Min). 30
Time:
Local Alarm Reminder Time (Min). 0
Time:
6.11. Warning time
When alarm group restrictions are used and areas are programmed for timed disarm, a
warning will sound (if a warning time is programmed) indicating the areas are about to
arm. The duration this warning will sound is programmed in this menu (0 – 255 minutes)
When a warning time is set, an audible alert is provided for the warning period preceding
the expiry. It MUST always be shorter than the shortest alarm group restriction time.
Always set the warning time to a time shorter than any Alarm group restriction
disarmed time.
See Alarm group restrictions (page 98) and Alm/grp restriction 1 disarmed time.
6.12. Disarmed alarm delay time
Determines the delay time (0 - 255 seconds) before an alarm from a delayed disarmed
alarm is reported to the central station. The delay time is ignored if another delayed zone
type has already been activated.
The delay is available for zone types 8, 11, 22 and 40. See Zone databaseTable 1
(page 17) for more information.
6.13. Suspicion time
The suspicion time is the length of time that a camera continues to operate after a
suspicion zone type has switched to normal state. The zone types that use this record are
7, 40, and 47.
The suspicion time is available for zone types 7, 40 and 47. See Zone database Table 1
(page 17) for more information.
6.14. Service time available
User menu 17 can be used to give access to service technicians. The alarm group for the
technician needs timezone 25 to be assigned. When a user enables the service
technician, timezone 25 will be valid during the service time (0 – 255 min).
See Alarm groups (page 51), Timezones (page 95) and the Manager’s guide.
6.15. Local alarm reminder time
The time that can elapse between acknowledging a local alarm and a re-alarm occurring,
including the audible alert (if the cause of the local alarm is not fixed).