System information

ATS2000/3000/4000/4500 Programming manual
54
NO
Prompt With List of Areas
*-Change 0 - Skip:
NO - Can User Activate Keypad Duress
*-Change 0 - Skip:
NO
Reset System Alarms
*-Change 0 - Skip:
NO
Disable Auto-Uninhibit
*-Change 0 - Skip:
5.1.5. List of areas
Select whether the areas assigned to a user are displayed during the arm/disarm
procedures.
YES After the user has entered a PIN code and pressed [ON] or [OFF], the areas
assigned to the user are displayed. The user can then select from the
arm/disarm options (e.g., specific areas, all areas, etc.).
This feature is useful when a user can control several areas but usually only
arms/disarms specific areas.
NO The areas assigned to the user are not displayed. Areas are immediately
armed/disarmed once the user has entered a PIN code and pressed [ON] or
[OFF].
Press 0 to go to the user menu items available.
5.1.6. Keypad duress
Enables the use of the duress facility using a code.
YES A code can be entered on a keypad to activate duress.
NO Duress cannot be activated. A duress code is treated as an invalid code.
Refer to the Manager’s Guide for further information on duress.
Press 0 to go to the user menu items available.
5.1.7. Reset system alarm
This record allows the alarm group to reset latching system alarms. System alarms are
conditions, such as DGP tamper, siren fail, low battery, report fail, etc.
YES A user with this alarm group can reset the latching system alarms.
NO A user cannot reset latching system alarms.
Press 0 to go to the user menu items available.
If this record is set at YES, Alarm system control must also be set to YES and
Latching systems alarms has to be set to YES (see System options, page 67).
5.1.8. Disable auto uninhibit
Determines that inhibited zones are uninhibited on disarming the area the zone belongs
to.