System information

ATS 2000/3000/4000/4500 Programming manual 47
Y
ES
Entry/Exit Buzzers
* - Change 0 - Skip
NO
Timed Lockout
* - Change 0 - Skip
NO
Cards Arm After 3 Badges
* - Change 0 - Skip
Y
ES - Disable Status LED's
* - Change 0 - Skip
See Table 3 on page 44 for further information on options available to arming stations.
3.2.15. Enable entry/exit buzzers
YES Enable buzzer for entry/exit timers.
NO No entry/exit timers on buzzer.
!
Entry time must be >10 seconds.
3.2.16. Timed lockout
YES On a code tamper, the RAS will lockout for 90 seconds.
NO Only event reported. The RAS will be available.
A code tamper: 5 consecutive wrong codes.
3.2.17 Cards Arm After 3 badges
This is an added option to arm an assigned area. When set to YES, 3 badges of a valid
card will arm the assigned area(s).
The 3 badges must occur within 10 seconds. If not, they will not be recognised for
arming.
The default is set to NO.
3.2.18. Disable Status LED's
This option disables the optical indicators on the BUS device card readers. The option to
enable or disable the status LED's will have to be set by the user because not all non -
LCD BUS devices are card readers therefore this option will have to be set based on the
hardware connected.
If this option is set to YES, the panel, when polling / commanding the card reader RAS, it
will not set any of the LED bits in the packet. This will result in the LED's not being active.
Limitation: Certain card reader settings override the status of command packet
LED bits - i.e. LED's remain illuminated even though LED bits are disabled. In
order to use this feature, it may be necessary to alter card reader configurations.
Altering card reader configurations:
For the ATS1170 Smart Door Controller:
Menu 5 - Led 1 Options: Led 1: Door Unlocked Only
For the ATS1190 Smart Card Reader:
Menu 1-Leds On-Line: 1-Blue Led: Door Open Only