System information

ATS2000/3000/4000/4500 Programming manual
46
NO
Arm/Disarm Using One Key
* - Change 0 - Skip
NO
Cards Auto Disarm
* - Change 0 - Skip
NO
Cards Always Arm/Disarm
* - Change 0 - Skip
NO
AlmGrp Restriction Disarm Only
* - Change 0 - Skip
NO
Reset From RAS Without Code
* - Change 0 - Skip
3.2.10. Arm/disarm using one key
YES Provides an option to arm or disarm areas by pressing the number of the area
without [enter], after having entered the user code.
NO Normal alarm control.
!
This option is only available for areas 1-8.
See Table 3 on page 44 for further information on options available to arming stations.
3.2.11. Cards auto disarm
YES Allows cards to disarm areas without using the [OFF] key.
NO Only the door is unlocked, except if Card always arms/disarms is set to YES or
the [ON]/[OFF] key is used.
See Table 3 on page 44 for further information on options available to arming stations.
3.2.12. Card always arms/disarms
YES Allows cards to arm/disarm areas without using the [ON]/[OFF] keys. Also
Toggle has to be set to YES.
NO Normal alarm control.
See Table 3 on page 44 for further information on options available to arming stations.
The card user's alarm group and the arming station's (reader's) alarm group must
both allow arm and/or disarm functions before a card can be used to arm/disarm.
3.2.13. Reset from RAS without code
YES Allows users to reset alarms by pressing [ENTER][ENTER] (show alarms)
followed by 0 [ENTER]. The areas in alarm have to be assigned to the arming
stations alarm group.
NO Reset only with user code.
See Table 3 on page 44 for further information on options available to arming stations.
3.2.14. Alarm group restrictions to disarm only
YES Users with alarm group restrictions can only disarm or delay automatic arming.
It cannot be used for alarm group restrictions with arm and reset.
NO There is no restriction.