System information

ATS2000/3000/4000/4500 Programming manual
32
NO
Keypad Buzze
r
*- Change 0 - Skip
NO
Make All Events 24 Hou
* Change 0 - Skip
Y
ES
Event Flag 2, Armed Alarm
* - Change 0 - Skip
1.1.16. Internal Siren Event Flag
Select if the Internal siren event flag should be activated. The Internal siren event flag is
assigned in the Area database.
YES The Internal siren event flag specified in the area database is activated when
the zone generates an alarm, and all the areas assigned to the zone are
armed.
NO The Internal siren event flag will not be triggered by an alarm in this zone.
For the Internal siren event flag to operate, you must also program the Internal
siren event flag number in the area database for each of the areas that activate
internal sirens and that are assigned to the zone. Refer to Area database (page
36). See also Zone Event flag (page 31).
1.1.17. External Siren Event flag
Select if the External siren event flag should be activated. The External siren event flag is
assigned in the Area database.
YES The External siren event flag specified in the area database is activated when
the zone generates an alarm, and all the areas assigned to the zone are
armed.
NO The External siren event flag will not be triggered by an alarm in this zone.
For the External siren event flag to operate, you must also program the External siren
event flag number in the area database for each of the areas that activate internal sirens
and that are assigned to the zone. Refer to Area database (page 36).
1.1.18. Keypad buzzer
The keypad buzzer can be activated during an
alarm.
YES When the zone generates an alarm, the keypad buzzer is activated on the
keypads that control the areas assigned to the zone.
NO An alarm on the zone will not trigger the buzzer.
See also Zone Event flag (page 31).
1.1.19. Make all events 24 hour
Used to activate all event flags on alarm.
YES All armed and disarmed alarm event flags are triggered when the zone
generates an alarm, regardless if the status of the area.
NO The armed and disarmed alarm flags are triggered depending on the status of
the area(s) assigned to the zone
See also Zone Event flag (page 31).
1.1.20. Trigger event flag 2, armed alarm
YES Event flag 2 is triggered when the zone generates an alarm and the area is
YES – Internal Siren, Program in DB
* - Change, 0 - Skip
YES – External Siren, Program in DB
* - Change, 0 - Skip