System information

ATS2000/3000/4000/4500 Programming manual
26
Zone type Description
54. Camera 7 Film Out Generates an alarm when camera 7 is out of film.
55. Camera 8 Film Out Generates an alarm when camera 8 is out of film.
56. Firedoor if No TZ41 If Timezone 41 is invalid, the zone has the following function:
Generates a local alarm when the area is disarmed but does not report
it to the central station.
This alarm can only be acknowledged by entering "USER CODE [OFF]
AREA [ENTER]" on the arming station.
Generates an alarm when the area is armed.
If Timezone 41 is valid, the zone is disabled.
Example: Fire door or emergency door.
Note: You need to program the local alarm reminder time (see Timers, page
61) and to link timezone 41 to an output (see Event to output, page 104).
57. Technical Report &
Screen
When the zone is activated or tampered, it reports to the central station and
puts the zone event text on the display. A restore is sent when the zone
switches to normal state.
Example: Temperature alarm on freezer
Note: You need to program the zone event text. See System options on
page 67.
58. Technical Screen When the zone is activated, opened or shorted, it puts the zone event text
on the display.
Example: Temperature alarm on freezer
Note: You need to program the zone event text. See System options on
page 67.
59. 24 Hour Alarm If No
Tz 41
If Timezone 41 is invalid, the zone has the following function:
Generates an alarm regardless of the status of the area.
If timezone 41 is valid, the zone is disabled.
Note: You need to program the local alarm reminder time (see Timers, page
61) and to link timezone 41 to an output (see Event to output, page 104).
60. Exit Terminator This zone type is used to terminate an exit time. If the zone switches from
active to normal, the exit time will be terminated and the area(s) are
completely armed.
61. Do NOT use Do NOT use this zone type.
62. Do NOT use Do NOT use this zone type.
63. Do NOT use Do NOT use this zone type.
64. Do NOT use Do NOT use this zone type.
65. Engineering reset
switch
This zone type allows you to perform an engineer reset via an input.
Note: You need to program the correct area to perform the reset.
66. Final door set This zone type is used to shorten the exit timer when the sensor associated
with this input is activated, normally on an exit door. When activated, it
shortens the exit timer to 4 seconds.(If ~ is needed, set the Exit Time to 0)