System information
ATS 2000/3000/4000/4500 Programming manual 21
Zone type Description
14. Access No Arm Check
• Generates no alarm when the area is disarmed.
• Generates an alarm when the area is armed and no entry/exit timer for
the area is active.
The zone may be activated when arming the area.
Example: PIR in hallway.
Note: You need to program the Entry Exit Time. See Area database on
page 36 for more information.
15. Firedoor
• Generates a local alarm when the area is disarmed.
Automatically activates an audible alert on arming stations assigned to
the same areas (regardless of the event flag programming). The only
event flag activated (as specified in the zone database) is the zone
event flag.
This local alarm can be reset by entering "[ENTER] [ENTER] 0
[ENTER]" or "USER CODE [OFF] AREA [ENTER]" on the arming
station to stop the audible alert and cancel the event.
If the zone remains activated, it generates a new local alarm after the
programmed local alarm reminder time.
• Generates an alarm when the area is armed.
Example: Firedoors or emergency doors
Note: You need to program the local alarm reminder time. See Timers on
page 61 for more information.
16. 24Hr Local Mains Fail It is not used in standard commercial versions of the ATS control panel. It
generates a local alarm, and activates an audible alert.
17. Do NOT use Do NOT use this zone type.
18. Report Fail Generates a local alarm. Activates an audible alert on arming stations
assigned to the same areas.
Activates FAULT LED on all arming stations and generates LCD fault
display message.
19. Report Fail LED Activates FAULT LED on all arming stations and generates LCD fault
display message.
20. Zone to Event Flag
24Hr
When activated, opened or shorted, it only activates the zone event flag.
Example: Doorbell.
21. Firedoor With User
Code
• Generates a local alarm when the area is disarmed but does not report
it to the central station, no audible alert on arming stations.
This alarm can only be acknowledged by entering "USER CODE [OFF]
AREA [ENTER]" on the arming station.
• Generates an alarm when the area is armed.
Example: Fire door or emergency door.