System information

ATS 2000/3000/4000/4500 Programming manual 19
Zone type Description
1. Disarmed alarm
Generates an alarm when the area is disarmed and reports it to the
central station.
Generates no alarm If the area is armed.
Example: Hold-up button.
2. Armed alarm
Generates no alarm when the area is disarmed.
Generates an alarm when the area is armed.
Example: Internal door, PIR (movement detector).
3. Entry/Exit Alarm
Generates no alarm when the area is disarmed.
When the area is armed, the exit timer starts and activating the zone
will generate no alarm. If the zone is activated and the exit time has
expired, the entry timer starts. When the entry time has expired, an
alarm will be generated.
The zone has to be closed when arming the area.
Example: Front door.
Note: You need to program the entry/exit time. See Area database on page
36 for more information.
4. Access zone
Generates no alarm when the area is disarmed.
Generates an alarm when the area is armed and the exit timer for the
zone has expired and the entry timer is not running.
The zone has to be closed when arming the area.
Example: PIR at entrance.
Note: You need to program the entry/exit time See Area database on page
36 for more information.
5. 24 Hour Alarm
Generates an alarm regardless of the status of the area.
Example: Panel tampers, fire, panic alarm
6. Pulsed Keyswitch When the zone switches from normal state to active, the functions of the
programmed alarm group are performed.
Example: Keyswitch next to Front door.
Note: You need to program alarm groups (see Alarm groups, page 51).
7. Camera Suspicion
Zone
When this zone is activated, cameras in the areas that are assigned to
the zone will be activated.
When the zone de-activates, the cameras continue to operate for the
programmed suspicion time.
Example: Suspicion button.
Note: You need to program the Suspicion Time. See Timers on page 61 for
more information.