System information

ATS2000/3000/4000/4500 Programming manual
18
0 [ENTER] Delete the word or variable. All words or variables are
deleted from this point onwards.
[ENTER] Press the ENTER key again to save the displayed
information and move to the next menu option display.
Using your own text words
If the library does not contain the correct text words, they can be
programmed in the menu Program text (page89. They have to be
programmed before they can be used.
1.1.2. Zone type
The zone type determines exactly how the zone will function in given circumstances.
Each zone type will behave differently. Most zone types require an area, but zone types
that affect the status of areas (zone types 6, 31, 34, 35) need alarm groups.
!
The zone type is important and influences much of the remaining programming and
functions of the system. Consequently, you must take considerable care when
programming zone types.
Armed and Disarmed
Armed or disarmed apply to the status of an area. If an area is armed, certain zone types
will go into alarm when the zone is activated. Other zone types only go into alarm when
the area is disarmed.
Tamper alarms
When the dual zone option (see System options, page 67) is set to YES, a short or open
circuit on most zone types will generate a tamper alarm. If set to NO, an open or short
circuit is the same as an activated zone.
Zone types that are not used to generate alarms do not generate tamper alarms, e.g.
technical or camera zone types.
Entry/exit times
Where entry/exit times are referred to, the time used is the longest entry/exit time
programmed for any of the areas assigned to the zone.
!
Camera Count Zone types (Types 23-26 and 36-39) must always be connected directly
to the ATS control panel zones and not to DGP zones.
Table 1. Zone types
Zone type Description
0. No zone type
programmed
Does not generate any alarm
1: Type 3; Entry Exit Alarm
Type