System information

ATS 2000/3000/4000/4500 Programming manual 165
LCD arming stations - Models ATS1100, ATS1105
Condition Possible cause
All the LED’s on the arming station are flashing. The dipswitches may be incorrectly set (the
address set on the arming station may be
incorrect and therefore polling to the arming
station is not being acknowledged).
The system databus line may be connected
incorrectly.
The arming station is not being polled (it may not
have been included in arming stations to be
polled when programming arming stations).
LED’s do not appear to be indicating the correct
condition.
The arming station type may have been defined
incorrectly:
LCD arming station must be set to YES.
The arming station appears to be going off-line
and on-line (indicated by the "RAS Fail"
message on the LCD).
The termination may be incorrect. See
Installation guide - Cabling.
An error is indicated when a code is entered on
the keypad (seven beeps).
An invalid PIN code may have been used.
The arming station may not have been
programmed with an alarm group.
The alarm group of the PIN may not permit
access at this arming station.