System information

ATS2000/3000/4000/4500 Programming manual
164
TROUBLESHOOTING
ATS control panel - Model ATS2000/3000/4000/4500
Condition Possible cause
The master LCD arming station (RAS address 1)
has all LED’s flashing and displays the “System
Fault” message.
The system databus line may be connected
incorrectly.
The address links on the RAS may be incorrectly
set.
The panel is not communicating with arming
stations and/or data gathering panels.
The system databus line may be connected
incorrectly.,
RAS and/or DGP numbers to be polled may not
be programmed, or may not match the
addresses set on the units.
Earth loop in cabling.
The arming stations and/or data gathering
panels appear to be going off-line and on-line
(indicated by RAS/DGP fail LED’s.
The system databus line may be connected
incorrectly.
The termination may be incorrect. TERM links
may not have been removed where necessary.
See Installation guide - Cabling
Zone goes into alarm while the area is disarmed. The zone is wired incorrectly causing a tamper
condition (open circuit or short circuit) instead of
active condition. E.O.L. resistors may be
installed incorrectly.
See the wiring diagrams in the installation guide.
Unable to assign alarm groups when
programming Users.
No alarm groups have been programmed with
the option “Can This Alarm Group be Assigned
to Users” set to YES.
If a code other than the Master User code (User
1) is being used to access “Program Users”, the
alarm group assigned to it may not allow the
function.
See Programming Guide, Programming option 5.
Panel is not reporting to central station The telephone line connections may be wired
incorrectly. See wiring diagrams in the
installation guide.
The central station receiver does not support the
programmed protocol.
The account number in Programming menu 9,
may be programmed incorrectly.
Phone number 1 MUST be programmed.
No central station is programmed to report the
event. See Zone database and Area database.