160
Type No Class Sub-class Condition CID SIA
Alarm E205 FA
Tamper E383 FT
Inhibit E570 FB
Alarm restore R205 FR
Tamper Restore R383 FJ
48 Fire Supervisory 205
Inhibit Restore R570 FU
Alarm E206 FA
Tamper E383 FT
Inhibit E570 FB
Alarm restore R206 FR
Tamper Restore R383 FJ
49 Fire Supervisory 206
Inhibit Restore R570 FU
The list of system events depends on the selection of the protocol type being large or
small. The small protocols only report summarised events. The large format reports as
much as possible (see Table 109 and Table 11 10).
Table 109 and Table 11 10 show a list of events to be reported split up to Contact ID and
SIA. Contact ID reports most events separately. Contact ID not only reports the event and
the point or user, but also the area. SIA reporting does not. SIA also uses an offset to
events reported from DGP’s (+300) or RAS’s (+400).
Table 109. Overview of small reporting format.
Contact ID SIA Description
Event Area Pt/User Event Pt/User
Duress Code Entered (Any Code No) E120 00 C 008 HA C 401-464
Duress Code Restored R120 00 C 008 HR C 401-464
Area Armed C402 01-16 U 001-999 CL U 001-999
Area Disarmed O402 01-16 U 001-999 OP U 001-999
RAS Offline (Any RAS No) E143 00 C 001 ET 000
RAS Online (Any RAS No) R143 00 C 001 ER 000
DGP Offline (Any DGP No) E143 00 C 002 ET 000
DGP Online (Any DGP No) R143 00 C 002 ER 000
DGP Mains Failure (Any DGP No) E301 00 C 004 AT 000
DGP Mains Restore (Any DGP No) R301 00 C 004 AR 000
DGP Battery Low (Any DGP No) E302 00 C 005 YT 000
DGP Battery Restore (Any DGP No) R302 00 C 005 YR 000
DGP Fuse Failure - - - ET 000
DGP Fuse Restore - - - ER 000
DGP Siren Monitor Fail (Any DGP No) E320 00 C 007 TA 000
DGP Siren Monitor Restore (Any DGP
No)
R320 00 C 007 TR 000
DGP Tamper (Any DGP No) E145 00 C 006 TA 000
DGP Tamper Restore (Any DGP No) R145 00 C 006 TR 000
DGP 16 CPU Restart E305 00 C 003 - -
RAS Tamper (Any RAS No) - - - TA 000