System information
ATS 2000/3000/4000/4500 Programming manual 153
REPORTING
Reporting in an ATS panel is divided in zone event reporting and system events. Zones
use reporting classes and sub-classes that can be programmed per zone. In Reporting
Class Database a selection can be made regarding the conditions to report per class.
Table 89 shows an overview of the reported event per sub-class and condition. The
column CID holds the reported Contact ID event. SIA holds the SIA event.
Table 89. Overview of reported events per sub-class
Type No Class Sub-class Condition CID SIA
Alarm E100 MA
Tamper E383 TA
Inhibit E570 MB
Alarm restore R100 MR
Tamper Restore R383 TR
1 Medical Medical 100
Inhibit Restore R570 MU
Alarm E101 MA
Tamper E383 TA
Inhibit E570 MB
Alarm restore R101 MR
Tamper Restore R383 TR
2 Medical 101
Inhibit Restore R570 MU
Alarm E102 MA
Tamper E383 TA
Inhibit E570 MB
Alarm restore R102 MR
Tamper Restore R383 TR
3 Medical 102
Inhibit Restore R570 MU
Alarm E110 FA
Tamper E383 TA
Inhibit E570 FB
Alarm restore R110 FR
Tamper Restore R383 TR
4 Fire Fire 110
Inhibit Restore R570 FU
Alarm E111 FA
Tamper E383 TA
Inhibit E570 FB
Alarm restore R111 FR
Tamper Restore R383 TR
5 Fire 111
Inhibit Restore R570 FU